iCOM

Controls Training and Service Manual

Service Menu: Set Alarm Parameters S200 series: Page 1 of 6

Menu Line

Parameter

Default

Range

S201 Password

-

-

S202

Return Sensor Alarms

Enabled

Disabled or Enabled

S203

High Return Temperature

80ºF

34 - 210ºF

S204

Low Return Temperature

65ºF

34 - 210ºF

S205

High Return Humidity

60%

1 – 99%

S206

Low Return Humidity

40%

1 – 99%

S207

Sensor A Alarms

Disabled

Disabled or Enabled

S208

High Temperature Sensor A

90ºF

34 - 210ºF

S209

Low Temperature Sensor A

55ºF

34 - 210ºF

S210

High Humidity Sensor A

70%

1 – 99%

S211

Low Humidity Sensor A

30%

1 – 99%


Service Menu: Set Alarm Parameters: Page 2 of 6

Menu Line

Parameter

Default

Range

S212 Password

-

-

S213

Customer Input 1

Water alarm

See note

S214

Customer Input 1 Active When

Closed

Open or Closed

S215

Customer Input 2

Water alarm

See note

S216

Customer Input 2 Active When

Closed

Open or Closed

S217

Customer Input 3

Water alarm

See note

S218

Customer Input 3 Active When

Closed

Open or Closed

S219

Customer Input 4

Water alarm

See note

S220

Customer Input 4 Active When

Closed

Open or Closed

S221

Warning Activates Alarm Relay

Yes

Yes or No

S222

Reset Disabled Alarms

No

Yes or No


Note: Customer Inputs 1, 2, 3 and 4 messages may be selected from Smoke
Detected, Water Alarm, Condensate Pump Alarm, Flow Alarm, Standby Pump,
Standby Unit.

76