iCOM

Control Training and Service Manual

6.

Each set of unit control boards must be set up individually, then connected to

the network switch and checked before the next board can be setup

6a.

Large Displays and Control Boards must each be programmed with a

different IP Address.

Example: Display: 192.168.254.001
Example: Control Board: 192.168.254.010

6b. Each

Display and Control Board in the

iCOM network must have the

same Gateway IP address.

Example: Gateway IP: 192.168.254.75

6c. Each

Display and Control Board in the

iCOM network must have the

same Netmask IP address.

Example: Netmask IP = 255.255.255.000


6d.

The Unit to Unit (U2U) address must be programmed in the necessary

order for setup.

Example: Unit Display: 33 – 64 and Unit Control Board: 1 - 32

43