P34: reheat devices, P35: infrared humidifier devices – Liebert iCOM Microprocessor TM-10098 User Manual
Page 109
iCOM
Controls Training and Service Manual
P22: Glycool Valve (Std. Pressure Actuator)
P22-1:
24 VAC Out (Close Q18) P22-4:
DCV
Signal
P22-2: DCV
Signal
P22-5:
E2 (24 VAC Gnd)
P22-3:
24 VAC Out (Open Q17)
P22-6:
+5 VDC
P32: Compressor Devices
P32-1: 24 VAC Out (LLSV1)
P32-8:
24 VAC
P32-2: E1 (LLSV1)
P32-9:
24 VAC (HP1 Alarm)
P32-3: 24 VAC Out (LLSV2)
P32-10: 24 VAC Out (C1)
P32-4: 24 VAC Out (OL/ KL1/ HP1)
P32-11:
E1 (C1)
P32-5: 24 VAC Out (OL/ KL2/ HP2)
P32-12: 24 VAC Out (C2)
P32-6: 24 VAC (HP1)
P32-13: E2 (C2)
P32-7: 24 VAC (HP2)
P33: Compressor Devices
P33-1: 24 VAC Out (CUV1/ DSV1)
P33-7:
24 VAC (OL/ KL2 Alarm)
P33-2: E1 (CUV1/ DSV1)
P33-8:
24 VAC
P33-3: E2 (LLSV2)
P33-9:
24 VAC (HP2 Alarm)
P33-4: 24 VAC Out (CUV2/ DSV2)
P33-10:
P33-5: E2 (CUV2/ DSV2)
P33-11:
P33-6: 24 VAC (OL/ KL1 Alarm)
P33-12:
P34: Reheat Devices
P34-1: 24 VAC Out (RS1/ RS2/ RS3) P34-7:
no connection
P34-2: E3 (RS1/ RS2/ RS3)
P34-8:
24 VAC Out (RH3)
P34-3: E3 (GCD/ BR)
P34-9:
no connection
P34-4: 24 VAC Out (RH1/ HGRS)
P34-10: E3 (RH1/ HGRS/ RH2/ RH3)
P34-5: no connection
P34-11:
no connection
P34-6: 24 VAC Out (RH2)
P34-12: 24 VAC Out (GCD/ BR)
P35: Infrared Humidifier Devices
P35-1:
24 VAC Out (H)
P35-4:
E4 (HMV)
P35-2: E3
(H)
P35-5: E3
(HS3)
P35-3:
24 VAC Out (HMV)
P35-6:
24 VAC Out (HS3)
P36: Basic Unit Connections
P36-1: 24 VAC Out (Filter Clog)
P36-9:
no connection
P36-2: 24 VAC (Filter Clog Alarm)
P36-10: E2
P36-3: 24 VAC Out (MF)
P36-11: No connection
P36-4: 24 VAC Out (AS Switch)
P36-12: No connection
P36-5: 24 VAC (AS Alarm)
P36-13:
K3 (Common: TB75)
P36-6: 24 VAC (MF Ovld Alarm)
P36-14: K3 (N.O.: TB76/ R3)
P36-7:
24 VAC
P36-15:
K3 (N.C.)
P36-8: E4
(MF)
108