iCOM

Control Training and Service Manual

Service Menu Parameters

The Service menu display allows the user to customize the various unit settings for
site specific operation. The factory default password to access the service menu
items for programming is “501”. The Service Menu selections include the following
choices in the order shown:

•

Set Point Parameters

•

Unit Diary

•

Standby Settings Parameters

•

Maintenance / Wellness Setting Parameters

•

Diagnostic / Service Mode Parameters

•

Set Alarm Parameters

•

Sensor Calibration / Setup Parameters

•

System / Network Setup Parameters

•

Operations Setup Parameters

•

Service Contacts Parameters



Service Menu: Set Point Parameters S100 series: Page 1 of 2

Menu Line

Parameter

Default

Range

S101 Password

-

-

S102

Temperature Setpoint

73ºF

41 - 104ºF

S103

Humidity Setpoint

50%

1 – 80%

S104

Humidity Control Type

Yes

Yes or No

S105

Supply Limit

Disabled

Disabled or Enabled

S106

Supply Limit Temp Value

41ºF

41 - 77ºF

S107

Autoset Enable

Yes

Yes or No

S108

Temperature Proportional Band

7ºF

2 - 54ºF

S109

Temperature Integration Time

0

0 – 5 minutes

S110

Temperature Deadband

0

0 - 36ºF

S111

Short Cycle Control

Yes

Yes or No