Lennox Hearth Electronic LMDV-3530-CNM User Manual

Page 16

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

16

A. Plan the vent run -

Analyze the vent routing and determine the

types and quantities of sections required

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2"

(572 mm), 34-1/2" (876 mm) and 46-1/2" (1181

mm) net section lengths are available. Plan the

vent lengths so that a joint does not occur at the

intersection of ceiling or roof joists. Make allow-

ances for elbows as indicated in Figure 24.

Maintain a minimum 1" (25 mm) clearance to

combustibles on the vertical sections. Clear-

ances for the horizontal runs are; 3" (76 mm)

on top, 1" (25 mm) on sides, and 1" (25 mm)

at the bottom.

H1

V

V1

H

u

Ceiling

Firestop / Spacer

(SV4.5VF)

v

Wall Firestop/

Spacer (SV4.5HF)

u

Ceiling

Firestop / Spacer

(SV4.5VF)

V

H1

H

V1

u

Ceiling

Firestop / Spacer

(SV4.5VF)

v

Wall Firestop/

Spacer (SV4.5HF)

Example: If 20 feet total (H+H

1

)

horizontal vent run is needed,

then 4 feet minimum of (V) verti-

cal vent will be required.

This table shows a 1(V) to 5(H)

ratio. For every 1 foot of (V)

vertical, you are allowed 5 feet

of (H+H

1

) horizontal run up to

a maximum total horizontal run

of 20 feet.

An elbow is acceptable as 1 foot

of vertical rise except where

an elbow is the only vertical

component in the system. See

Figure 37.

Table D

H +

H

1

Maximum

V Minimum

feet

(meter)

feet

(meter)

5

(1.524)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

H + H

1

= 20 feet (6.096 m) Max.

V + V

1

+ H + H

1

= 40 ft. (12.192 m) Max.

u

When using Secure Flex, use Firestop / Spacer SF4.5VF

v

When using Secure Flex, use Firestop / Spacer SF4.5HF

Table C

H

+H

1

Maximum

H

Maximum

V Minimum

feet

(meter)

feet

(meter)

feet

(meter)

5

(1.524)

2

(0.610)

1

(0.305)

10

(3.048)

4

(1.219)

2

(0.610)

15

(4.572)

6

(1.829)

3

(0.914)

20

(6.096)

8

(2.438)

4

(1.219)

V + V1 + H + H1 = 40 feet (12.2 m) Max

H = 8 feet (2.438 meters) Max.

H + H1 = 20 feet (6.096 meters) Max.

Example: If 20 feet total (H+H

1

) horizontal vent run is needed,

then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V)

vertical, you are allowed 5 feet of (H+H

1

) horizontal run up to a

maximum total horizontal run of 20 feet.

u

When using Secure Flex, use Firestop / Spacer SF4.5VF

v

When using Secure Flex, use Firestop / Spacer SF4.5HF

Figure 32 - Top Vent - THREE ELBOWS

Figure 31 - Rear Vent - THREE ELBOWS

VERTICAL VENT FIGURES/TABLES

(CONTINUED)

HORIZONTAL (OUTSIDE WALL)

TERMINATION SYSTEM
Figure 33 on Page 17, and Figures 34 to 42 on

Pages 18 to 21 and their associated Horizontal

Vent Table illustrate the various horizontal

venting configurations that are possible for

use with these appliances.

Secure Vent pipe

applications are shown in these Figures;

Secure

Flex pipe may also be used. A Horizontal Vent

Table summarizes each system’s minimum and

maximum vertical and horizontal length values

that can be used to design and install the vent

components in a variety of applications.

Both of these horizontal vent systems terminate

through an outside wall. Building Codes limit or

prohibit terminating in specific areas. Refer to

Figure 7 on Page 6 for location guidelines.
Secure Vent SV4.5 direct vent system compo-

nents are unitized concentric pipe components

featuring positive twist lock connection, (refer

to Figure 22 on Page 13). All of the appli-

ances covered in this document are fitted with

collars having locking inclined channels. The

dimpled end of the vent components fit over

the appliance collar to create the positive twist

lock connection.