5

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

12

X

Roof Pitch is X/12

2 FT

MIN.

2 FT MIN.

Lowest

Discharge

Opening

H*

*H = MINIMUM HEIGHT FROM ROOF TO

LOWEST DISCHARGE OPENING OF VENT

TERMINATION HEIGHTS FOR VENTS ABOVE

FLAT OR SLOPED ROOFS

Horizontal Overhang

Vertical

Wall

Vent

Termination

Storm Collar

Concentric

Vent Pipe

Flashing

1 inch (25.4 mm) Minimum

Clearance to Combustibles

Figure 5

Vertical Vent Termination Clearances

VENT TERMINATION CLEARANCES

These instructions should be used as a guide-

line and do not supersede local codes in any

way. Install vent according to local codes,

these instructions, the current National Fuel

Gas Code (ANSI-Z223.1) in the USA or the

current standards of CAN/CGA-B149.1 and

-B149.2 in Canada.
Terminate multiple vent terminations according to

the installation codes listed above.
Terminate single vent caps relative to building

components according to Figure 5.

Horizontal Vent Termination Clearances

The horizontal vent termination must have a minimum of 3" (76 mm) clearance to any overhead

combustible projection of 2 1/2" (64 mm) or less. See Figure 6. For projections exceeding 2 1/2"

(64 mm), see Figure 6. For additional vent location restrictions refer to Figure 7 on Page 8.

Figure 6

Note - See Figure 35 on Page 20 for the exterior wall recess

allowances of the square horizontal termination.

MANUFACTURED HOME

REQUIREMENTS

This appliance may be installed in an after-

market permanently located, manufactured

home (USA only) or mobile home, where not

prohibited by local codes.

Cet appareil peut être installé dans un maison

préfabriquée (É.-U. seulement) ou mobile déjà

installée à demeure si les réglements locaux

le permettent.

Manufactured Home installations must be

installed in accordance with these instructions

and the following standards / codes:

• Manufactured Home Construction and

Safety Standard Title 24 CFR, Part 3280, or

the current Standard for Fire Safety Criteria

for Manufactured Home Installations, Sites

and Communities ANSI / NFPA 501A in the

USA, and CAN / CSA Z240 MH Mobile Home

Standard in Canada

• (when applicable) The American National

Standard for Manufactured Homes (NCSBCS

/ ANSI A225.1 - latest edition).

CAUTIONS

Ensure that the cross members

are not cut or weakened during

installation. The structural integ-

rity of the manufactured home

floor, wall, and ceiling / roof must

be maintained.

This appliance must be grounded

to the chassis of the manufac-

tured home in accordance with

local codes or in the absence of

local codes, with the National

Electrical Code ANSI / NFPA 70

- latest edition or the Canadian

Electrical Code CSA C22.1 - latest

edition.

Termination Heights For Vents

Above Flat Or Sloped Roofs

Ref. NFPA 54 / ANSI Z223.1, 7.6

Roof Pitch

* Feet

* Meters

Flat to 6/12

1.0

0.3

6/12 to 7/12

1.25

0.38

7/12 to 8/12

1.5

0.46

8/12 to 9/12

2.0

0.61

9/12 to 10/12

2.5

0.76

10/12 to 11/12

3.25

0.99

11/12 to 12/12

4.0

1.22

12/12 to 14/12

5.0

1.52

14/12 to 16/12

6.0

1.83

16/12 to 18/12

7.0

2.13

18/12 to 20/12

7.5

2.29

20/12 to 21/12

8.0

2.44

The vent / air intake termination clearances

above the high side of an angled roof is as

shown in the following chart:

3"

(76 mm)

12"

(305 mm)

Combustible Projection greater

Horizontal Vent Termination Clearances

Combustible Projection

2-1/2 inches or less in length

18"

(457 mm)

Ventilated

Soffit

Unventilated

Soffit

than 2-1/2 inches in length

Termination Kit

Side Elevation View

Termination Kit

All horizontal terminations

may be located as close as

6” (152mm) to any

(non-combustible and

combustible) exterior

sidewall. This distance

may be decreased to 2”

(51mm) for non--

combustible exterior

sidewalls only, if the

SV4.5HT-2 termination

is used.