Lennox Hearth Electronic LMDV-3530-CNM User Manual

Page 7

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

7

Hearth Extension A hearth extension is not required with this appliance. If a hearth extension is

used, do not block the lower control compartment door. Any hearth extension used is for appearance

only and does not have to conform to standard hearth extension installation requirements.

Wall Finishes / Surrounds / Mantels

Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach

the area defined by the appliance front face (black sheet metal). Never allow combustible materials

to be positioned in front of or overlapping the appliance front face. See Figure 61 on Page 30.

Non-combustible materials, such as surrounds and other appliance trim, may be installed on the

appliance front face with these exceptions: they must not cover any portion of the removable glass

panel or louvers.

Vertical installation clearances to combustible mantels vary according to the depth of the mantel.

See Figure 8. Mantels constructed of non-combustible materials may be installed at any height

above the appliance opening; however, do not allow anything to hang below the hood.

MINIMUM CLEARANCES TO COMBUSTIBLES

4 (102)

2

(51)

4

(102)

6

(152)

8

(203)

10

(254)

12

(305)

6 (152)

10 (254)

14 (356)

12 (305)

8 (203)

Top of

Appliance

inches (millimeters)

Mantel Depth

Note - Hood shown as positioned with louvered panels.

Figure 8 -

Minimum Mantel Clearances

MINIMUM CLEARANCES

Inches (millimeters)

Back

1/2 (13)

0 (0) Spacers

Sides

1/2 (13)

0 (0) Spacers

Top Spacers

0 (0)

Floor

0 (0)

Bottom of Appliance

To Ceiling

64 (1626)

Vent

3 (76)

Top

*

1 (25.4)

Sides & Bottom

SERVICE CLEARANCES

Feet (meters)

Front

3 ft. (0.9 m)

Table 8

Appliance and Vent Clearances

The appliance is approved with zero clearance to

combustible materials on all sides (as detailed in

Table 8), with the following exception: When the

unit is installed with one side flush with a wall, the

wall on the other side of the unit must not extend

beyond the front edge of the unit. In addition, when

the unit is recessed, the side walls surrounding

the unit must not extend beyond the front edge

of the unit. See Figure 4.

*Note: 3 in. (75 mm) above any horizontal/in-

clined vent component.

**Note: See Page 8, Step 1 for clearance

requirements to the nailing flange located

at each side of the unit and any screw heads

adjacent to it.

Combustible materials may project beyond the sides of the fire-

place opening as long as they are kept within the shaded areas

illustrated here.

5 (127)

8-1/4

(209)

14

(356)

12 (305)

19

(483)

Combustible Materials

Allowed In Shaded Area

“Safe Zone”
Combustible Walls

shown in dark gray

Minimum Distance to Unprotected Side Wall

Top View of

Fireplace

45

o

At 14" minimum

side wall clearance,

a combustible wall

can project to any

length.

Protected wall shown in white

Inches (millimeters)

Figure 10

At 8-1/4" side

wall clearance, a

combustible wall

can project 12"

Shelf Above Fireplace With Rear Venting

Do not insulate the

space between the

appliance and the

area above it.

Shelf Height

(

see table)

*Shelf Height

(

see table)

Do not insulate the

space between the

appliance and the

area above it.

Shelf Above Fireplace With Top Venting

Figure 9 -

Shelf Height Minimum Clearances

Model No.

Combustible Shelf Height - Inches (millimeters)

Top Vent - with One 90 Degree Elbow

Rear Vent - Straight Out the Back

Secure Vent

Secure Flex

(flex elbow)

Secure Vent

Secure Flex

LMDVT-3328

*44-1/2 (1130)

*46-1/4 (1175)

N/A

N/A

LMDVR-3328

N/A

N/A

33-1/4 (845)

33-1/4 (845)

LMDV-3530

*46-1/2 (1181)

*48-1/4 (1226)

35-1/4 (895)

35-1/4 (895)

LMDV-4035

*51-1/2 (1308)

*53-1/4 (1349)

40-1/4 (1022)

40-1/4 (1022)

* Includes 3” clearance to combustibles (required above vent components)

When the unit is

installed with one side

flush with a wall, the

wall on the other side

of the unit must not

extend beyond the front

edge of the unit.

Advertising