Installation – Lennox Hearth II-T C FS User Manual

Page 20

Advertising
background image

INSTALLATION

INSTALLING ADVANTAGE II-T C INS (CONTINUED)

PAGE 20

Full Chimney Reline

Recommended for All Chimney Installations

Horizontal Vent Through Masonry Chimney Structure








.

USA & Canada – Requires an approved noncom-

bustible hearth or floor protector, 3/8” / (10 mm)

millboard or equivalent (k = .84, r = 1.19) to ex-

tend 6” / 150 m19-20m to the front of the glass

door.

Do not block opening at front of insert (below

door).

Seal Chimney top with steel
plate and/or pipe support

Listed Rain Cap

Approved Liner for Factory
Built (ZC) Fireplaces and
Masonry Fireplaces is
2100HT (degree F.) liner
listed to UL 1777 or ULC
S635. The liner must be se-
curely attached to the insert
flue collar and the chimney
top.

18” Min.

(457 mm)

to Mantel

1” Min.

(25 mm)

to Trim

♦ 6” Min. Floor
Protection

Optional Posi-
tive Flue
Connection

Clean
Out Tee

USA – The insert may
be installed as a Hori-
zontal Vent (through
chimney structure) in
Masonry Fireplaces if
local code permits.

IN CANADA – Installing as a Horizon-
tal Vent is NOT allowed. The fireplace
chimney must be fully lined.

18” Min.

(457 mm)

to Mantel

♦ 6” Min. Floor
Protection

1” Min.

(25 mm)

to Trim

Mantel

Mantel

IMPORTANT NOTES:

A flexible corrugated chimney
liner has much greater resis-
tance to the flow of flue gases
than does a rigid liner. For this
reason we recommend that a
larger, 4” liner be used on ver-
tical runs exceeding 15 feet or
that rigid venting be used as
illustrated on this page (see
Full Chimney Reline).

If a flexible corrugated chimney
liner is used, it must be fully
extended to eliminate any sag-
ging and to improve the ex-
haust flow.