PLANNING YOUR INSTALLATION

PAGE 8

MANUFACTURED (MOBILE) HOME INSTAL-
LATION
Freestanding Model – Advantage II-T C FS
In addition to the standard installation instructions,
the following instructions may be required by lo-
cal, state or federal building codes:
• Stove must be permanently bolted to the floor.
• An outside air inlet must be provided for com-

bustion and be unrestricted while unit is in use.
Use a galvanized or stainless steel pipe for the
duct (the outside air inlet on the stove is 1 5/8"
diameter).

• Stove must be permanently electrically

grounded to the steel chassis of the home. The
location selected for ground attachment to the
stove must be dedicated for this purpose.

• See pages 13 through 18 for additional informa-

tion on venting requirements.

• Do not install appliance in a sleeping room.
• The structural integrity of the manufactured

home floor, walls, ceiling and roof must be
maintained.


NOTE: The grounding of this product, at installa-

tion, must comply with NFPA-70 stan-
dards, CSA C22.1 in Canada, as well as
any local codes.

Model – Advantage II-T C FS


Pedestal Air Inlet

MANUFACTURED (MOBILE) HOME EXHAUST VENT PIPE
INSTALLATION GUIDELINES
Use only “PL” pellet vent pipe listed to UL 641 and ULC
S609. The pipe should extend at least 3 feet above the part
of the roof through which it passes. The top of the pipe
should be at least 2 feet above the highest required elevation
of any part of the manufactured (mobile) home within 10 feet
of the pipe (see page 14, Manufactured [Mobile] Home
Chimney Height Requirements
).

If the exhaust vent exits the manufactured (mobile) home at a
location other than the roof, and exits at a point 7 feet or less
above the ground level on which the manufactured (mobile)
home is position a guard or method of enclosing the pipe
shall be provided at the point of exit for a height of up to 7
feet. The openings, if any, in this guard shall not allow a 3/4”
rod to pass through. A 1/2” rod could pass through but should
not be able to touch the pipe when inserted through the open-
ing a distance of 4 inches.

24 ¾”

12 ½”

6 7/8”

25”

Outside Air Inlet

1 5/8" diameter

Bolt

Bolt

Floor Protector

Steel Chassis

Ground

To Chassis

Floor

www.PelletKing.com