The RUN relay contact at TB2 terminals 7 and 8 is a dry contact

rated at 1 Amp (Resistive load) at 125VAC. You may use it in an
external circuit as long as the voltage does not exceed 125 VAC
(limitation of the terminal strip).


You may use an auxiliary relay if you need more power, or if you

need more contacts, as shown in the drawing at the left. You should
use a 48VDC coil (highly recommended) since this reduces the burden
on one supply. The diode is a general purpose type rated for at least 1
Amp at 100VDC PIV (1N4002 or equivalent).


The ZERO SPEED output at TB2 terminal 1 is an open collector

NPN transistor, rated at 50 ma at 50 VDC. The ZERO SPEED
transistor turns on at about 10 RPM and turns off at about 5.RPM

The transistor emitter is at drive common and it may interface

directly with a PLC as a sinking input.

The output can operate a relay as shown in the top drawing on

the left. The transistor returns to drive common, so it is not possible to
use a 48VDC relay with the drive’s supplies. If you use a 24VDC relay,
the current must be as low as possible. The diode is a general
purpose type.

The ZERO SPEED relay will chatter at very low speeds. You can

overcome this with a latching circuit that releases at the first dropout of
the zero speed relay.

The FAULT output at TB1 terminals 12 and 13 is the output

transistor of an optical coupler. The coupler’s rating is 100VDC @ 50
ma.

Connect a FAULT relay with a 48VDC coil as shown in the

bottom figure at left. The external FAULT relay energizes when the
drive completes power-up and de-energizes when a fault occurs.
The diode is a general purpose diode.


The Model 1000AR has an ENABLE output terminal at TB2

terminal 2. The ENABLE output is an open collector transistor that
turns on when the drive is ready to accept a reference for speed
input, whether in RUN or in JOG. You must use a 24VDC coil on the
ENABLE output.


The ENABLE output shuts off if there is a trip or when the drive

shuts off either on Emergency Stop or a non-ramp stop, or when the
JOG input is released.


The internal RUN relay drops out on RAMP STOP. The

ENABLE output remains energized throughout the RAMP STOP
sequence. Use ENABLE for functions which must continue when the
motor is running.

TB2

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

R+

R-

ZERO

SPEED
RELAY

24VDC Coil

RUN

RELAY

48VDC Coil

R+

R-

TB1

16

15

14

13

12

11

10

9

8

7

FAULT

OUTPUT

ISOLATOR

48V

DC

24V

DC

9

3

2

1

TB2

ENABLE

FAULT

-24VDC

11

6

6

5

4

8

7

10

+24VDC

ENABLE