POWERTEC Model 1000AR Drive Start Up and Troubleshooting Chart

NOTE: This chart assumes standard control connections

and no options installed which affect speed control.

CC = Current Controller board.

Is

RUN LED

ON

?

To

Page 5

From

Page 3

Page 4

Is

ENBL LED

ON

?

Press START

Button and

Release

(See note

above)

+24V

TB2-13(+)

TB2-16(-)

?

+24V

TB2-12(+)

TB2-16(-)

?

Check

"START Button"

connections

No

+24V

TB2-11(+)

TB2-16(-)

?

Yes

Check

"STOP Button"

connections

No

+24V

TB5-3(+)

TB2-16(-)

?

Yes

Check "EMERG

STOP Button"

connections

No

+24V

TB5-1(+)

TB2-16(-)

?

Yes

Check Bus

Loader for

Green LED

Disconnect all

wires connected

to TB2-10

+24V

TB2-10(+)

TB2-16(-)

?

Yes

Check

disconnected

wires

Replace Speed

Controller Board

This sequence

assumes that standard

control connections

are being used.

See page 21.

The voltages given

must be at the

indicated terminals

unless otherwise

indicated.

No

Yes

Press and

HOLD START

Button

Is

RUN LED

ON

?

No

Replace Speed

Controller Board

+24V

TB2-11(+)

TB2-16(-)

?

Yes

+24V

TB2-12(+)

TB2-16(-)

?

No

No

Check

"STOP Button"

connections

Yes

No

Check "EMERG

STOP Button"

connections

Yes

Release

START

Button

Release

START

Button

No

PJ1

on CC

in RESET

position

?

Yes

Set PJ1 jumper on

Current Controller

board to either INT

or MAN position

No

Is

PL LED

on CC

ON

?

No

Yes

+24V

TB2-10(+)

TB2-16(-)

?

Replace Current
Controller Board

>21VDC

<21VDC

No

Yes

Shut off power

Unplug P3 and TB2

Reapply power

+24V

TB2-10(+)

TB2-16(-)

?

Replace Speed

Controller Board

>21VDC

Shut off power

Plug In P3

Reapply power

+24V

TB2-10(+)

TB2-16(-)

?

<21VDC

Replace

Capacitor Board

Check TB2

Connections

>21VDC

Is

IOC LED

on CC

ON

?

No

Is

OVUV

LED on CC

ON

?

Perform IOC

tests (page 50)

Yes

Perform OV/UV

tests (page 50)

Yes

Replace Cable

on P3 Connector

No

TRIP

+24V

TB2-10(+)

TB2-16(-)

?

No

No

<21VDC

Check Motor
Thermal and

wires

Yes

Yes

Yes

Advertising