I/o protection, Understanding short-circuit-proof devices – National Instruments NI 9475 User Manual

Page 10

Advertising
background image

NI 9475 Operating Instructions and Specifications

10

ni.com

I/O Protection

The NI 9475 is short-circuit proof in accordance with IEC 1131-2
and provides overcurrent protection.

Understanding Short-Circuit-Proof Devices

Each channel on the NI 9475 has circuitry that protects it from
current surges resulting from short circuits. Whether the module
suffers damage from these overcurrent conditions depends on the
following factors:

The amount of current through the channel

The amount of time the current is above the current limit

The frequency of the current surges

When the amount of current through the DO pin is greater than
13 A, the channel trips and goes into an overcurrent state. In an
overcurrent state, the channel turns off and the module is not
damaged. If the current through DO is between 6 A and 13 A, the
state of the channel is indeterminate and depends on factors such
as the current level, the temperature, and the power supply.

Advertising