Figure 2. installing the cfp-do-403, Wiring the [c]fp-do-403 – National Instruments FP-DO-403 User Manual

Page 3

Advertising
background image

© National Instruments Corp.

3

[c]FP-DO-403

Figure 2. Installing the cFP-DO-403

Wiring the [c]FP-DO-403

The FP-TB-x terminal base has connections for each FP-DO-403
output channel and for an external supply to power field devices.
The cFP-CB-x connector block provides the same connections for
the cFP-DO-403.

Each channel has one output terminal, V

OUT

. The output channels

share eight V

SUP

terminals and eight COM terminals. All of the

channels are referenced to the COM terminals. The V and V

SUP

terminals are all internally connected, as are the C and COM
terminals.

Use a 5–30 VDC external power supply for the output channels.
The power supply must provide enough current to power all of the

1

cFP I/O Module

2

Captive Screws

3

cFP Controller Module

4

Screw Holes

5

cFP Backplane

2

2

1

3

5

4

4