Figure 3. Wiring for Low-Current Applications

Wiring for High-Current Applications

If your application requires more than 2 A combined current
through all channels of the [c]FP-DO-403, wire your application
as shown in Figure 4. Install a 2 A maximum, fast-acting fuse
(F2A 250V) in series with each load as shown.

Figure 4. Wiring for High-Current Applications

COM

V

OUT

V

C

[c]FP-DO-403

Load

+

5–30 VDC

External Power

Supply

V

SUP

V

OUT

2 A Max

User-Supplied

Fuse

Load

COM

V

OUT

V

C

[c]FP-DO-403

Load

+

5–30 VDC

External Power

Supply

V

SUP

V

OUT

2 A Max

User-Supplied

Fuse

Load

2 A Max

User-Supplied

Fuse

2 A Max

User-Supplied

Fuse