Horizontal termination, 90° h – Napoleon Fireplaces GDS25P User Manual

Page 12

Advertising
background image

12

W415-0547 / C / 07.25.06

V

1

HORIZONTAL TERMINATION

20

10

0

5

10

15

90

100

120

110

30

40

50

60

70

80

130

140

150

20

See graph to determine
the required vertical rise V

T

for the required horizontal
run H

T

.

For vent confi gurations requiring more than one 45º and 90°
elbow the following formulas apply:

Formula 1: H

T

< 4.2 V

T

Formula 2: H

T

+ V

T

< 24.75 feet

FIGURE 7

REQUIRED
VERTICAL
RISE IN
INCHES (V

T

)

HORIZONTAL VENT RUN PLUS OFFSETS IN FEET

when

(H

T

) > (V

T

)

Simple venting confi guration (only one 45º and 90° elbow)

Example 2:

V

1

= 4 ft

V

2

= 1.5 ft

V

T

=

V

1

+

V

2

= 4 ft + 1.5 ft = 5.5 ft

H

1

=

2

ft

H

2

=

1

ft

H

3

=

1

ft

H

4

=

1.5

ft

H

R

=

H

1

+

H

2

+

H

3

+

H

4

= 2 + 1 + 1 + 1. 5 = 5.5 ft

H

O

= .03(one 45º elbow + three 90º elbow -135º)

=.03(315-135)=5.4ft

H

T

=

H

R

+

H

O

= 5.5 +5.4 = 10.9 ft

H

T

+ V

T

= 10.9 + 5.5 = 16.4 ft

Formula 1:

H

T

< 4.2 V

T

4.2

V

T

= 4.2 x 5.5 = 23.1 ft

10.9 < 23.1

Formula 2:

H

T

+ V

T

< 24.75 feet

16.4 < 24.75

Since both formulas are met, this vent confi guration is
acceptable.

H

4

90°

H

3

H

1

90°

H

2

90°

FIGURE 8

45°

The shaded area within the lines represents acceptable
values for H

T

and V

T

.

V

2