Lifebreath Clean Air Furnace CAF-02-MB User Manual

Page 24

Advertising
background image

24

In order for any appliance to work properly it must be set
up and tested by a knowledgeable technician.

The following conditions must be met prior to

start-up
1. Ensure that connecting water lines are purged and free of

debris.
Caution: solder or other debris may cause the furnace
pump or check valve to malfunction.

2. Blower wheel rotates freely inside its housing.

3. Wiring connections are tight.

4. Water is sitting in the "P" trap below the

HRV core.

5. All duct and pipe connections are sealed.

6. Check that styrene block is removed from under pump.

7. Front access door is on tight.

8. Fan speed selection:

a) Heating/Cooling - factory setting is at high speed and
can be changed in the electrical box to medium-high or
medium if required.
b) Ventilation - low speed is controlled by the
Thermostat Fan switch.

Once all of the necessary connections have been

made, the Clean Air Furnace Start-Up Procedure is

as follows:
1. Close shut-off valves separating the Clean Air Furnace

from the water heater.

2. Set up water heater according to manufacturer's instruc-

tions.

3. Purge air from unit. To do so, open the supply shut-off

valve to the furnace. Attach a garden hose to drain valve,
and drain water until you get a continuous flow. Close
the drain valve and purge the pump. To purge the air
from the pump, turn the large screw on the face of the
pump counterclockwise until water leaks out, then tight-
en. Open the supply shut-off valve.

4. Turn on power supply to Clean Air Furnace.

5. Switch the room thermostat to heat. The thermostat

should be set higher than the current room temperature in
order to energize the pump and commence the heating
cycle. (If the pump does not start, or the Clean Air
Furnace is not producing heat, refer to the
Troubleshooting Section in this manual.

6. Set room thermostat at desired temperature setting.

Start-Up Procedure

Advertising