Dimensions & clearances – Lifebreath Clean Air Furnace CAF-02-MB User Manual

Page 37

Advertising
background image

37

Top

Side

22.25"

(565 mm)

Supply Air

Ventilation
Supply Air
Inlet

Ventilation
Exhaust Air
Outlet

Return Air

Blower Section

(SERVICE CLEARANCE 1')

(SERVICE CLEARANCE 3')

Front

Latches

29.5"

(749 mm)

19"

(483 mm)

47.5"
(1207 mm)

6"

14"

(356 mm)

12"

(305 mm)

4”

(100 mm)

19”

(483 mm)

17.25”

(438 mm)

22”

(559 mm)

(150 mm)

6"

(150 mm)

29.5"

(749 mm)

Options
99-186

Weatherhoods, Two - 6" (150 mm)
c/w 1/4" (6 mm) mesh screen

99-130W

Remote Wall Mount Dehumidistat Control 24
VAC only

99-RSK6

6” (150 mm) back draft damper

99-104

DET - Digital Electronic Timer

Core

Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for ener-
gy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25°F (-4°C).

Filters

Washable air filters in exhaust and supply air streams of ventilation section, 1" (25 mm) pleated in return plenum side.

Case

Prepainted galvanized steel for superior corrosion resistance.

Dimensions & Clearances

Model

CAF-U-00-48-P16

Voltage

120 VAC 60 Hz

Hp

1/2

Amps (total)

10.6

*

Airflow (High)

.25 in wg

1888 CFM

.5 in. wg

1589 CFM

Ventilation

100 - 140 CFM

Airflow

Effectiveness

70%

(Aluminum Core)

Total Efficiency

50%

(Enthalpic Core)

Net Weight

132 lbs.

Shipping Weight

147 lbs.

* Airflow performance assumes an evaporator
coil static pressure loss of .25”WC.

Warranty
Units carry a lifetime warranty on the heat recovery (alu-
minum) core, a five year warranty on the energy recovery
(enthalpic) core and a five year replacement parts warranty
on all other components.

Note: Ventilation ports and return plenum

opening available off either side of cabinet.

All units conform to CSA and UL Standards.

Date: ___________________________________________

Tag: _____________________Qty:___________________

Project: _________________________________________

Engineer: _______________________________________

Contractor: ______________________________________

Supplier: ________________________________________

Quote#: _________________________________________

Submitted by: ____________________________________

Model CAF-U-00-48-P16