Specifications

These ratings are typical at 25

°C unless otherwise stated.

Electrical

Number of output channels.....................1

Output referencing ..................................Nonreferenced (floating)

Input range ..............................................0 to 10 V

Output range ...........................................0 to 20 mA

Voltage compliance ................................12.5 V

Maximum load resistance

5 mA ................................................2,500

Ω

10 mA ..............................................1,250

Ω

15 mA ..............................................830

Ω

20 mA ..............................................625

Ω

Absolute accuracy...................................0.1% of full-scale output range

Temperature drift ....................................0.5

μA/°C typ

1

μA/°C max

Power Requirement

Analog power .........................................175 mW max

+15 V...............................................5.8 mA max
–15 V ...............................................5.8 mA max

Digital power (

+5 V) ..............................645 mW

+5 V.................................................129 mA max