Using an External Loop Supply

In order for the current sink to operate properly with an external loop
supply, the voltage must be within the range of 3 to 42 V. If the voltage is
too high, overheating can occur and damage the module. Figure 4 shows
four configurations using an external loop supply.

Figure 4. Connecting the SCC-CO20 Using an External Loop Supply

When you use an external loop supply, the order of the supply and load does
not matter as long as you do not create a second loop through which current
flows. If both the supply and the load are grounded, connect the signals as
shown in Figure 5.

High
CMV

High
CMV

1

2

Load

SINK

+

SCC-CO20

ISO GND

I

a. Nonreferenced load and external voltage supply (two circuits)

b. Referenced load and external voltage supply (two circuits)

1

2

Load

SINK

+

SCC-CO20

ISO GND

I

1

2

Load

SINK

+

SCC-CO20

ISO GND

I

1

2

Load

SINK

+

SCC-CO20

ISO GND

I

+

+

0–20 mA

0–20 mA

0–20 mA

0–20 mA