ni.com

Module STATUS LED

The module STATUS LED is located on the front of the linking device,
between the two Fieldbus (H1 Network) connectors, as shown in
Figure B-1. It indicates whether the linking device is powered, configured,
and operating properly. Table B-2 shows how to interpret the STATUS
LED states.

Table B-1. Ethernet STATUS LED Flashes and Corresponding Error Conditions

Number

of Flashes

Error Condition

0 (stays lit)

The FBUS-HSE/H1 LD has not been configured with a
proper IP address.

1

The FBUS-HSE/H1 LD is in Reset mode. Switch the
FBUS-HSE/H1 LD back to Normal mode by powering
down the device and sliding the switch underneath the
module.

2

The FBUS-HSE/H1 LD has detected an error in its
firmware. This usually occurs when an attempt to
upgrade the firmware is interrupted. Repeat the
firmware upgrade process.

3

The FBUS-HSE/H1 LD cannot communicate with the
NIFBUS. Be sure that the NIFBUS is running on the
computer that you specified when you configured the
FBUS-HSE/H1 LD.

4 (or more)

The FBUS-HSE/H1 LD has detected an unrecoverable
error. Contact National Instruments for more
information of finding the cause of this error.

Table B-2. Interpretation of

FBUS-HSE/H1 LD

Module STATUS LED

LED State

Meaning

Off

No power to linking device

Flashing red
and green

The FBUS-HSE/H1 LD self-testing

Flashing green

Standby state

Solid green

Operational state