Cabling Options

This section describes the cabling options for accessing signals on the
TB-2708.

A 14-pin connector on the bottom of the TB-2708 provides access to
digital I/O signals. Use the MFIT-Pigtail Cable Assembly (part number
194123-01) to access digital signals on the TB-2708. The MFIT-Pigtail
Cable Assembly features a 14-pin I/O connector on one end and pigtail
conductors on the other end. The pigtail conductors on the cable assembly
can be used to terminate digital signals to the connector(s) your application
requires. Figure 5 and Table 3 list the pin assignments and wiring
information necessary for connecting the TB-2708 to DIO signals.

Figure 5. 14-Pin Digital I/O Connector

Table 3. TB-2708 Wiring Information for 14-Pos MFIT-Pigtail Cable

Assembly (Part Number 194123-01)

Pin Number

Wire Color

Signal Name

1

Black

GND

2

White

P0.0

3

Red

P0.1

4

Green

P0.2