WI1370 XP-400 Installation Instructions

Installation

Mounting the Panel

Mount the Panel close to an unswitched AC
source, a cold-water pipe ground, and a
telephone line connection.

Mounting the Keypad

A keypad should be located near an exit/entry
door. To remove the keypad from the backplate,
insert a small screwdriver into the slots at the
bottom of the keypad. Pull up on the
screwdriver to pop off the cover.

Up to 3 keypads can be connected on individual
wire runs with #22 AWG wire with a maximum
total cable length of 1000 feet. Each keypad
draws approximately 35 mA.






Wiring

Grounding the Panel

Connect the control-panel EARTH GROUND
screw to a metal cold-water pipe. Do not use a
gas pipe, plastic pipe or AC ground connections.
Use at least #16 AWG wire. Connect a wire
with a ground lug crimped or soldered onto one
end and connect it to the EARTH GROUND
screw in the cabinet.

AC Power and Battery Wiring

Complete all wiring before connecting the
battery or AC Power. Do not plug the
transformer into a switched outlet.

Telephone Wiring

Wire as shown in the wiring diagram in the back
of this manual.

WARNING

The FCC restricts the use of this equipment on
certain telephone lines. Read the FCC
statement on the back of this manual to ensure
compliance.

Burglary Zone Wiring

NAPCO’s EZ Zone Doubling

TM

is simple. Each

terminal has 2 zones, use an E (2.2 K) type
Zone Doubling Resistor for the primary zone

and a Z (3.9 K) type Zone Doubling Resistor for
the secondary zone.






Wire zones as shown in the wiring diagram (pg.
27). All resistors must be installed, even if the
zone is not used. If required, unsupervised
open circuit devices may be used instead of
closed circuit devices. Program the zone as an
Open Circuit Zone [06] (Zone Doubling Resistor
required). If necessary, use the voltage chart
below to verify proper voltages.





Keypad Wire Color

Control Panel Terminal

RED

12 (+PWR)

BLACK

13 (GND)

GREEN

14 (GREEN)

TABLE

1 K

EYPAD

W

IRING

Terminals

2.2 K Primary

3.9 K

3&4

Zone 1

Zone 4

5&4

Zone 2

Zone 5

6&7

Zone 3

Zone 6

TABLE

2 EZ Z

ONE

D

OUBLING

TM

Primary (2.2K) and Secondary (3.9K) zones normal

1.9 V

Secondary (3.9K) open

2.5 V

Primary (2.2K) open

3.2 V

Primary (2.2K) and Secondary (3.9K) open

5.0 V

Primary (2.2K) and/or Secondary (3.9K) shorted
(Sys. Trbl 7-Zone Trbl)

0.0 V

TABLE

3 V

OLTAGE

AT

T

ERMINALS

3&4, 5&4,

6&7