Dc power supply installation, Prerequisites, Dc power supply installation procedures – Nortel Networks NN46200-310 User Manual

Page 27

Advertising
background image

27

.

DC power supply installation

This chapter provides instructions to install the DC power supply in the
Ethernet Routing Switch 8300 chassis.

See Nortel Ethernet Routing Switch 8300 Administration, NN46200-604 for
the minimum Ethernet Routing Switch 8300 software version required to
support the hardware.

ATTENTION

Nortel recommends that you install each power supply on its own dedicated
branch circuit to ensure that a fault on another branch circuit does not cascade
to other branch circuits.

Prerequisites

Verify that you have the following tools and materials:

cable

crimping tool for crimping the lugs onto the cable

heat gun to shrink the tubing around the cable (optional)

7/16-inch hex wrench

Phillips screwdriver

Determine the minimum number of DC power supplies to be installed.
For more information, see

“Determining the minimum number of DC

power supplies” (page 28)

DC power supply installation procedures

This task flow shows you the sequence of procedures you perform to
install the duel input DC power supply in the Ethernet Routing Switch
8300. To link to any tasks, go to

“DC power supply installation navigation”

(page 28)

.

Nortel Ethernet Routing Switch 8300

Installation — DC Power Supply

NN46200-310

01.01

Standard

9 June 2008