Procedure steps, Preparing cables for installation – Nortel Networks NN46200-310 User Manual

Page 29

Advertising
background image

Preparing cables for installation

29

For more information, see Nortel Ethernet Routing Switch 8300 Installation
— Chassis, NN46200-309
.

Procedure steps

Step

Action

1

Add the total (3.3 V and 12 V) input power consumption
(wattage) for all components (modules and fan trays or cooling
modules).

2

Refer to the output power rating of the power supply based on
the input connection.

If either the individual or the combined power requirements for
the components exceed the power supply rating, you need to
add at least another power supply to your configuration.
For the 8005DI DC power supply specifications, see

“Model

8005DI DC power supply” (page 47)

. For the 8005DC power

supply specifications, see

“Model 8005DC power supply” (page

48)

3

Consider your redundant power supply needs. If one power
supply satisfies your system power consumption needs, a
second power supply provides redundancy. If two power
supplies satisfy your system power consumption needs, a third
power supply provides redundancy.

--End--

Preparing cables for installation

Prepare the cables for installation of the power supply of the Ethernet
Routing Switch 8300.

Nortel does not supply the cables for connecting the DC power supply to
the DC input power source. Select cables that comply with the electrical
code of the country where you use the DC power supply.

CAUTION

Risk of equipment damage

Make sure that the connection cable used with the DC power
supply is appropriate for use with the DC power source to which
the power supply connects. Consider gauge, flammability, and
mechanical serviceability when you determine which cables to
use.

Procedure steps

Step

Action

Nortel Ethernet Routing Switch 8300

Installation — DC Power Supply

NN46200-310

01.01

Standard

9 June 2008

Copyright © 2008 Nortel Networks

.