National Instruments NI 9229 User Manual

Page 6

Advertising
background image

NI 9229/9239

6

ni.com

Caution

For Zone 2 applications, install a protection

device between the input signal and the NI 9229/9239
input terminal. The device must prevent the input
channel-to-COM voltage from exceeding 85 V if there is
a transient overvoltage condition.

Caution

For Zone 2 applications, connected signals must

be within the following limit:

Capacitance .......................... 0.01

μF max

Special Conditions for Hazardous Locations Use in Europe

This equipment has been evaluated as Ex nA IIC T4 equipment
under DEMKO Certificate No. 07 ATEX 0626664X. Each module
is marked

II 3G and is suitable for use in Zone 2 hazardous

locations. If you are using the NI 9229/9239 in Gas
Group IIC hazardous locations or in ambient temperatures of
–40 °C

≤ Ta ≤ 70 °C, you must use the device in an NI chassis that

has been evaluated as EEx nC IIC T4, Ex nA IIC T4, or
Ex nL IIC T4 equipment.

Advertising