Nt -8106-ti-r t, Channel analog input – NotaTech 8000SeriesI/O User Manual

Page 14

Advertising
background image

4

Contact:

®

NovaTech Process Solutions, LLC
11500 Cronridge Dr., Suite 110
Owings Mills, MD 21117

T: 410.753.8300
Toll Free: 800.253.3842

www.novatechweb.com

. 4 RTD or resistance* source inputs
. Function defined by configuration
. 2-, 3- or 4-wire RTD types accommodated

Module Specifications

Inputs

Number of channels ..........................................................................4
RTD input (2,3, or 4 wire)
....................................................Pt100 to BS1904/DIN43760/IEC 75
........................................................Ni120; jPt100 to JIS C1604: 1989

Input Ranges

Input Type

Range

Resistance

Consult NovaTech for availability

RTDs: Pt100

– 200 to + 850 °C

jPt100

– 200 to + 510 °C

Ni120

– 60 to + 320 °C

Input resistance range (span)..........................................0 to 500 Ω

Accuracy (% of span)

Tamb

(RTD & Ω inputs)

25°C

± 0.05%

+10 to + 40°C

± 0.1%

– 40 to + 70°C

± 0.2%

RTD excitation current ..............................................200 μA (nom.)
Resolution ..........................................................15 bits plus sign bit
Common mode rejection................................> 80 dB @ 50/60 Hz
Series mode rejection.......................................> 40 dB @ 50/60 Hz
Isolation (any channel to Railbus) .............................250 V ac rms
Open circuit bleed current.........................................0.5 μA (nom.)

NT

-8106-TI-R

T

Image Description

4-channel Analog Input

RTD and Ω

Configurabe Parameters

Sensor type....................................................................user selection
Input deadzone ..................................................user defined value
Selectable input filtering....off /2-reading avge./running avge.
Drive on open circuit fault................................. disabled /upscale
Channel status...........................................................active/ inactive
Offset (2-wire RTD mode).................................user defined value

Response Times

Signal change to availability on Railbus
...........................................................................................180 ms (min.)
..........................................................................................840 ms (max.)
O/C sensor detection.................................................................≤ 10 s

Safety

FM non-incendive field wiring parameters (each channel)
...............V

oc

= 10.5 V; I

sc

= 3.6 mA; C

a

= 14.9 µF; L

a

= 1000 mH

Power Supplies

Railbus (12V) current...................................................150 mA (typ.)
.........................................................................................200 mA (max.)
Bussed Field Power .......................................................not required

Mechanical

Module Key Code .............................................................................C1
Module width ............................................................................42 mm
Weight............................................................................................200 g

Field Terminals

Field Wiring

Recommended

Field Terminal

Compatible

Field Terminal

General Purpose

NT-8606-FT-RT

RTD

-

Class 1, Div 2

or Zone 2 hazard-

ous area

NT-8606-FT-RT

RTD

-

*Consult NovaTech for availability.

NovaTech 8000 Series I/O Family

Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks

are properties of their respective owners. NovaTech is a registered

trademark of NovaTech, LLC. The information in this literature is

subject to change without notice and is not to be construed as a

warranty. DS_8106_0607

Advertising