Nt -8115-do-dc, Channel discrete output – NotaTech 8000SeriesI/O User Manual

Page 25

Advertising
background image

5

Contact:

®

NovaTech Process Solutions, LLC
11500 Cronridge Dr., Suite 110
Owings Mills, MD 21117

T: 410.753.8300
Toll Free: 800.253.3842

www.novatechweb.com

. 8 powered outputs
. Controls solenoids and relays
. Common load supply of up to 60 V dc
. Discrete or pulsed outputs
. 1A per channel switched current
. 2–60 V dc bussed field power required

Module Specifications

Outputs

Number of channels ...........................................................................8
Output voltage range.........................................................2–60 V dc
ON voltage drop.............................................................0.25 V (max.)
OFF leakage current ...................................................1.0 mA (max.)
Switched current per channel ††
Continuous *................................................................................1 A
For < 100 ms.................................................................................4 A
For < 20 ms...................................................................................6 A

Configurable Parameters

Output initialization state....................................predefined
value
Fail-safe.................................................predefined value/last value
Output .....................discrete, momentary or continuous pulse‡
Pulse width.....................................................................2 ms to 130 s

Response Time

Response time
From Railbus command to output change ..........1 ms (max.)

Power Supplies

Railbus (12V) current......................................................45 mA (typ.)
...........................................................................................70 mA (max.)
Bussed Field Power .........................................................2 to 60 V dc

NT

-8115-DO-DC

Image Description

8-channel Discrete Output

2–60 V dc, non-isolated, module powered

Mechanical

Module Key Code..............................................................................B6
Module width ............................................................................42 mm
Weight............................................................................................200 g

Field Terminals

Field Wiring

Recommended

Field Terminal

Compatible

Field Terminal

General Purpose

NT-8604-FT-FU

Fused

NT-8602-FT-ST

Standard †

Class 1, Div 2

or Zone 2 hazard-

ous area

NT-8611-FT-FU

Non-arcing,

Fused

NT-8610-FT-NA

Non-arcing †

† Alternative fusing in the field wiring is recommended if it is
not provided in the field terminal.
†† The total instantaneous switched current should not
exceed the following:
10 A for < 100 ms
18 A for < 20 ms
*Limited to 6 A per module
‡Consult NovaTech for availability

NovaTech 8000 Series I/O Family

Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks

are properties of their respective owners. NovaTech is a registered

trademark of NovaTech, LLC. The information in this literature is

subject to change without notice and is not to be construed as a

warranty. DS_8115_0607