. 8 discrete isolated inputs
. 230 V ac field voltage sources
. User definable input threshold
. Pulse counting option

Module Specifications

Inputs

Number of channels ...........................................................................8
OFF voltage............................................................................< 68 V ac
ON voltage ...........................................................................> 168 V ac
Wetting current .........................................1 mA (nom.) @ 230 V ac
Max. input voltage ................................................................265 V ac
Frequency ............................................................................50 / 60 Hz

Configurable Parameters

Selectable input filter ...........................fast, slow or user defined
(User defined permits 0 to 512 ms values in 2ms steps)
Latch inputs................................................................enable /disable
Latch polarity......................................latch on high / latch on low
Pulse counting ..........................................................enable /disable

Response Time

I/O response time
Field event to new data available on Railbus....33 ms (max.)

Power Supplies

Railbus (12V) current......................................................40 mA (typ.)
...........................................................................................60 mA (max.)
Bussed Field Power .......................................................not required

Mechanical

Module Key Code..............................................................................E5
Module width ............................................................................42 mm
Weight............................................................................................170 g

NT

-8113-DI-AC

Image Description

8-channel Discrete Input

230 V ac, isolated, sinking

Field Terminals

Field Wiring

Recommended

Field Terminal

Compatible

Field Terminal

General Purpose

NT-8602-FT-ST

Standard †

NT-8604-FT-FU

Fused

Class 1, Div 2

or Zone 2 hazard-

ous area

NT-8610-FT-NI

Non-arcing †

NT-8611-FT-FU

Non-arcing,

fused

† External fusing of the Field Power supply is recommended
in order to protect the field wiring.

NovaTech 8000 Series I/O Family

Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks

are properties of their respective owners. NovaTech is a registered

trademark of NovaTech, LLC. The information in this literature is

subject to change without notice and is not to be construed as a

warranty. DS_8113_0607

Advertising