Nt -8122-di-dc, Channel discrete input, 24 v dc, isolated, sinking – NotaTech 8000SeriesI/O User Manual

Page 20

Advertising
background image

0

Contact:

®

NovaTech Process Solutions, LLC
11500 Cronridge Dr., Suite 110
Owings Mills, MD 21117

T: 410.753.8300
Toll Free: 800.253.3842

www.novatechweb.com

. 16 input channels
. 24 V dc field voltage sources
. Individually isolated channels
. User definable input threshold
. Pulse counting option

Module Specifications

Inputs

Number of channels ........................................................................16
OFF voltage...........................................................................< 3.4 V dc
ON voltage .............................................................................> 11 V dc
Wetting current ........................................2.8 mA (nom.) @ 24 V dc
Minimum pulse width detected ...............................................5 ms
Max input freq in pulse counting mode (no-debounce)100 Hz
Maximum voltage
Input ......................................................................................30 V dc
Reverse input ................................................................. – 25 V dc
Isolation (Any Channel to railbus) .....................................250 V ac
Isolation (channel to channel) ......................................150 V peak

Configurable Parameters

Selectable input filter ...........................fast, slow or user defined
(User defined permits 0 to 512 ms values in 2ms steps)
Pulse counting ..........................................................enable /disable

Response Time

I/O response time ............................................................5 ms (max.)
(Field event to new data available on Railbus)

Safety

FM non-incendive field wiring parameters (each channel)
......................V

max

= 30 V; I

max

= 100 mA; C

i

= 0 µF; L

i

= 0 mH

NT

-8122-DI-DC

Image Description

16-channel Discrete Input

24 V dc, isolated, sinking

Power Supplies

Railbus (12V) current......................................................90 mA (typ.)
.........................................................................................135 mA (max.)
Bussed Field Power .......................................................not required

Mechanical

Module Key Code .............................................................................E2
Module width ............................................................................42 mm
Weight............................................................................................210 g

Field Terminals

Field Wiring

Recommended

Field Terminal

Compatible

Field Terminal

General Purpose

NT-8617-FT-NI †

16 channel DI

-

Class 1, Div 2

or Zone 2 hazard-

ous area

NT-8617-FT-NI †

16 channel DI

-

† External fusing of the Field Power supply is recommended
in order to protect the field wiring.

NovaTech 8000 Series I/O Family

3AFE

OR

M

P

# HANNEL

2AILBUS

ILB

24V

DC

Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks

are properties of their respective owners. NovaTech is a registered

trademark of NovaTech, LLC. The information in this literature is

subject to change without notice and is not to be construed as a

warranty. DS_8122_0607

Advertising