Nt -8103-ai-tx, Channel analog input – NotaTech 8000SeriesI/O User Manual

Page 9

Advertising
background image

9

Contact:

®

NovaTech Process Solutions, LLC
11500 Cronridge Dr., Suite 110
Owings Mills, MD 21117

T: 410.753.8300
Toll Free: 800.253.3842

www.novatechweb.com

. 8 single-ended 4-20mA input channels
. Non-incentive field circuits
. 4-20mA
. 2- or 4-wire transmitters
. Open and short circuit detection
. 24Vdc bussed field power required

Module Specifications

Inputs

Number of channels ...............................................8, single-ended
Nominal signal range (span) ..........................................4 to 20 mA
Full signal range.................................................................1 to 23 mA
Out of range alarm
Lower threshold.............................................................> 23.5 mA
Upper threshold .............................................................< 0.5 mA
Output voltage (@ 20 mA)............................................13.5 V (min.)
Output current ..............................................................32 mA (max.)
Accuracy (over temp range) ...................................± 0.1% of span
Resolution ..................................................................................16 bits
Repeatability ................................................................0.05% of span
Isolation
(any channel to Railbus) .................................................100 V ac
(between channels)................................................................none

NT

-8103-AI-TX

Image Description

8-channel Analog Input

4–20 mA

Configurable Parameters

Input filter time constant .................................user defined value
Input dead zone .................................................user defined value
Drive on failsafe............................. disabled /upscale /downscale
Channel status.......................................................... active /inactive

Response Time

Signal change to availability on Railbus .................27 ms (max.)

Safety

FM non-incendive field wiring parameters (each channel)
..................V

oc

= 28.7 V; I

sc

= 33 mA; C

a

= 0.17 µF; L

a

= 11.0 mH

Power Supplies

Railbus (12V) current .....................100 mA (typ.)/150 mA (max.)
Bussed Field Power ..................................2-wire Tx 300 mA (max.)
(@ 24 Vdc ± 10%) 4-wire Tx 60 mA (max.)

Mechanical

Module Key Code .............................................................................A1
Module width ............................................................................42 mm
Weight............................................................................................200 g

Field Terminals (2-wire TX)

Field Wiring

Recommended

Field Terminal

Compatible

Field Terminal

General Purpose

NT-8602-FT-ST

Standard

NT-8604-FT-FU

Fused

Class 1, Div 2

or Zone 2 hazard-

ous area

NT-8601-FT-NI

Non-incendive

NT-8603-FT-FU

Non-incendive

Fused

Field Terminals (4-wire TX)

Field Wiring

Recommended

Field Terminal

Compatible

Field Terminal

General Purpose

NT-8615-FT-4W

-

Class 1, Div 2

or Zone 2 hazard-

ous area

NT-8615-FT-4W

-

NovaTech 8000 Series I/O Family

Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks

are properties of their respective owners. NovaTech is a registered

trademark of NovaTech, LLC. The information in this literature is

subject to change without notice and is not to be construed as a

warranty. DS_8103_0607

Advertising