. 8 single-ended 4-20 mA output channels
. Non-incendive field circuits
. HART pass-through
. HART variable and status reporting
. Valve positioners and remote indicators, etc.
. Open circuit detection on each channel
. 24 V dc bussed field power required

Module Specifications

Inputs

Number of channels ...............................................8, single-ended
Nominal signal range (span) ..........................................4 to 20 mA
Full signal range.................................................................1 to 23 mA
Open loop detection threshold ...............................0.7 ± 0.25 mA
Output compliance ..............................20 mA at 21.6 V dc supply
....................................................................................(into 700 Ω load)
Accuracy (over temp range) .................................± 0.25% of span
Resolution ..................................................................................12 bits
Isolation
(any channel to Railbus) .................................................100 V ac
(between channels)................................................................none

Configurable Parameters

Initialization state..................................................predefined value
Drive on fail-safe ................................predefined value/last value
Channel status.......................................................... active /inactive
HART variable and status reporting.....................enable /disable

NT

-8102-HO-IP

Image Description

8 Channel Analog Output

4–20 mA with HART®

Response Time

Signal change to availability on Railbus
4–20 mA mode .........................................................25 ms (max.)
HART mode......................................................0.75 s per channel

Safety

FM non-incendive field wiring parameters (each channel)
..................V

oc

= 28.7 V; I

sc

= 33 mA; C

a

= 0.17 µF; L

a

= 11.0 mH

Power Supplies

Railbus (12V) current ..................................................100 mA (typ.)
.........................................................................................150 mA (max.)
Bussed Field Power .................... 300 mA (max.) at 24 Vdc ± 10%

Mechanical

Module Key Code .............................................................................A4
Module width ............................................................................42 mm
Weight............................................................................................200 g

Field Terminals

Field Wiring

Recommended

Field Terminal

Compatible

Field Terminal

General Purpose

NT-8602-FT-ST

Standard

NT-8604-FT-FU

Fused

Class 1, Div 2

or Zone 2 hazard-

ous area

NT-8601-FT-NI

Non-incendive

NT-8603-FT-FU

Non-incendive

NovaTech 8000 Series I/O Family

3AFE

OR

-58

M0

2EGULATOR

/THER

CHANNELS

2AILBUS



"USSED

$!

#HANNEL

 M!

0

)

((#

Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks

are properties of their respective owners. NovaTech is a registered

trademark of NovaTech, LLC. The information in this literature is

subject to change without notice and is not to be construed as a

warranty. DS_8102_0607

Advertising