Nt -8116-do-ac, Channel discrete output – NotaTech 8000SeriesI/O User Manual

Page 27

Advertising
background image

7

Contact:

®

NovaTech Process Solutions, LLC
11500 Cronridge Dr., Suite 110
Owings Mills, MD 21117

T: 410.753.8300
Toll Free: 800.253.3842

www.novatechweb.com

. 8 powered outputs
. Controls solenoids and relays
. Common load supply of up to 265 V ac
. Discrete or pulsed outputs
. 1A per channel maximum
. 20–265 V ac bussed field power required

Module Specifications

Outputs

Number of channels ...........................................................................8
Output voltage range.....................................................20–265 V ac
Frequency ............................................................................50 / 60 Hz
ON voltage drop........................................................................< 1.2 V
OFF leakage current .................................................................< 4mA
Switched current per channel ††
Continuous.................................................................................1 A*
For < 100 ms.................................................................................5 A
For < 20 ms.................................................................................20 A
Minimum load current, per channel
@ 115 V ac...............................................................................11 mA
@ 230 V ac.................................................................................5 mA

Configurable Parameters

Output initialization state...................................predefined value
Fail-safe.................................................predefined value/last value
Output .....................discrete, momentary or continuous pulse‡
Pulse width.....................................................................2 ms to 130 s

Response Time

Response time (max.) ..2 ms + 1/2 cycle of mains frequency
(From Railbus command to output change)

Power Supplies

Railbus (12V) current......................................................75 mA (typ.)
..........................................................................................125mA (max.)
Bussed Field Power (voltage)....................................20 to 265 V ac

NT

-8116-DO-AC

Image Description

8-channel Discrete Output

20–265 V ac, non-isolated, module powered

Mechanical

Module Key Code .............................................................................F1
Module width ............................................................................42 mm
Weight............................................................................................220 g

Field Terminals

Field Wiring

Recommended

Field Terminal

Compatible

Field Terminal

General Purpose

NT-8604-FT-FU

Fused

NT-8602-FT-ST

Standard †

Class 1, Div 2

or Zone 2 hazard-

ous area

NT-8611-FT-FU

Non-arcing,

Fused

NT-8610-FT-NA

Non-arcing †

† Alternative fusing in the field wiring is recommended if it is
not provided in the field terminal.
†† Stated figures are for operation with unfused field termi-
nal. When operating with 2 A fused field terminal part no.
NT-8604-FT-FU, maximum switched current is 5 A inrush for
<10 ms pulse width at 0.1% duty cycle and <108 operations
*Limited to 3 A per module.
‡Consult NovaTech for availability

NovaTech 8000 Series I/O Family

Copyright © 2007 NovaTech, LLC. All rights reserved. All trademarks

are properties of their respective owners. NovaTech is a registered

trademark of NovaTech, LLC. The information in this literature is

subject to change without notice and is not to be construed as a

warranty. DS_8116_0607

Advertising