GEM-P1664 Installation Instructions

WI1424A 1/06



Page 55

The Factory Program of the GEM-P1664 will change with the release of the new version that complies with Security Industry As-
sociation False Alarm Reduction Control Panel-01 Standard (SIA FAR CP-01).

Out of Box Panel Operation

The following describes the new panel factory defaults:

The new SIA CP-01 compliant versions of the GEM-P1664 panels have a factory program that allows a locally functioning alarm
panel out of the box, programmed with all the non-reporting features required by the SIA CP-01 standard.

The new versions of the panels are manufactured with the following factory programmed features:

1.

All zones (64 in the GEM-P1664) are programmed for Priority, Selective Bypass, Alarm Output, Keypad Sounder on
Alarm and Abort Delay.

2.

Default User 1 Code = "123" and it is set up to arm Area 1 and be a user program code.

3.

Keypad Time/Date Display enabled.

4.

The reporting format is Ademco, Silent Knight Slow.

5.

Touch Tone with Rotary Back-up is enabled.

6.

Exit Delay = 60 seconds.

7.

Entry Delay 1 and 2 are both 30 seconds.

8.

AC Fail Report Delay is 60 minutes.

9.

Alarm and Pulse Alarm time-outs are 5 minutes.

10. Chime is set to 2 seconds.
11. Change Pulse Alarm to Cadence Alarm is enabled.
12. Auto Reset after Burglary Output Timeout is enabled.
13. 1422-Bit 6 "Chirp Output on Keyfob Arm/Disarm" is enabled.
14. 1424-Bit 0 "Automatic Interior Bypass/Easy Exit" is enabled.
15. 1423-Bit 7 "Select Alarm Output for Keyfob Chirp" is enabled.
16. 2053-Bit 0 "Exit Time Restart" is enabled.
17. 2053-Bit 1 "Sound Alarm on Exit Error" is enabled.
18. 2053-Bit 3 "Enable CP-01 Limits" is enabled.
19. 1417 "Abort Delay" is changed to 30 seconds.
20. Cancel Time ("Cancel Window Duration") is set to zero minutes.

The complete Easy Programming menu will appear upon initial entry into Dealer Program Mode. Subsequent entry into Dealer
Program Mode allows only a subset of the Easy Program Menu.

With this new SIA CP-01 compliant panel, the Easy Program Menu has been increased to allow several additional features to
be programmed in the Menu, rather than requiring that these features be programmed through the Direct Address programming
method. Note: Upon entering Dealer Program Mode, the above referenced factory program is immediately cleared and the
"Prior to CP-01 Changes" (see below) factory program is loaded. Therefore, if you enter Dealer Program Mode, you will be re-
quired to first enter Easy Program Mode and answer Easy Program Mode questions before making any needed changes to the
factory program via Direct Address Programming Mode.

Once the panel is removed from its box, you have three choices: (1) Do not enter Dealer Program Mode and complete the in-
stallation using the unmodified factory program; (2) Upload the Factory Default Program (above) to PCD-Windows, make de-
sired changes, and re-download this modified PCD-Windows program back to the panel; (3) Enter Dealer Program Mode in or-
der to allow the EZ Program Menu to appear, then answer "Yes" to the question "Enable CP-01 Features?".

A critical addition to the Easy Program Menu is the question “Enable CP-01 Features? Y/N”. If the answer to this question is
No” then the following changes to the program occur:

1.

All zones (64 in the GEM-P1664) are programmed for Priority, Selective Bypass, Alarm Output, Auto Reset and Swinger
Shutdown. Only the zones selected by the first EPM question “How many Zones” are programmed for Area 1.

2.

Default User 1 Code = "123" and it is set up to arm Area 1 and be a user program code.

3.

Keypad Time/Date Display enabled.

4.

All zones are programmed with report codes and as burg/fire alarm types depending on whether they were selected as
fire zones. Zones not selected as fire are burg type.

5.

The reporting format is selectable in the Easy Program Mode.

6.

Touch Tone with Rotary Back-up is enabled.

7.

Exit Delay = 60 seconds.

8.

Entry Delay 1 and 2 are both 30 seconds.

9.

AC Fail Report Delay is 60 minutes.

GEM-P1664 FACTORY DEFAULT DESCRIPTION