Smoke detectors & summar y of u l requirements, Summary of ul requirements – Napco Security Technologies GEM-P1664 User Manual

Page 8

Advertising
background image

X

GEM-P1664 Installation Instructions

L

NAPCO Security Systems

WI1424A 1/06



Page 8

Smoke Detectors, 4-Wire:

1. ESL 445AT, 445C, 445CT, 445CR, 445CRT
2. Hochiki America SLG-12 with YBC-RL4-RA Base
3. System Sensor 2312/24T; 1412; 1412TH; 2412TH
Subtract total smoke-detector alarm current from available standby current.
Note: Any normally-open devices that do not require power from the control panel, such as pull stations and

thermostats may be used if acceptable to the Authority having Jurisdiction.

Smoke detectors & Summar

y

of U

L

Requirements

UL Compatible Smoke Detectors (Providing UL Recognition or Listing)

Manufacturer

4-Wire

Smoke Detector

2-Wire

Smoke Detector *

Smoke Detector

Base

Napco

FW-4

FW-2

Sentrol






System

Sensor



449AT
449C
449CRT
449CST
449CSRT
449CSRH
449CSST

449CLT
449CSLT
449CTE
741U
742U

712U
722U
732U
711U
721U
721UT

731U

1112
2112

2112T
2112TSRB

2100
2100T

1100

701U
702U
702RE
702RU

Note: * Voltage Rating: 8.5-13.3 VDC, Maximum Number of Detectors: 10

SUMMARY OF UL REQUIREMENTS

Residential



Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits.



Initiating loops supervised if longer than 3 feet



FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors)



Minimum alarm timeout of 5 minutes



Maximum exit time: 60 seconds



Maximum entry time: 45 seconds



Do not program “Swinger Shutdown”, “Force Arming”, “Selective Bypass” or “50 ms Loop Response”



“Abort Delay” may not exceed 45 seconds



Program “Disable Callback Download”



Automatic dialer may not dial a police station number that has not been dedicated for such service



System must be tested at least weekly under AC/battery and Battery-Only conditions



Replace the rechargeable battery at least every 5 years



If the battery is heavily discharged, replace it or have it tested by a qualified technician



For silent panic, connect only to UL-listed holdup devices



All zones must be programmed for “Priority”



Do not program any zones for “Keyswitch Arming”



System must be serviced at least once every year



Residential Fire and Combination Residential Fire & Burglary must program “Residential Fire”



Keypad Expansion (EZM) Zones are not to be used as fire zones



Keypad Auxiliary is not to be selected



The GEM-K Series Keypads must have the indicators printed on the face label (Fire, Police and Auxiliary) covered by a
supplied label if not in use.