Roberts Gorden Vantage twin Fire Unitary Infrared Heater TF-250 User Manual

Page 13

Advertising
background image

SECTION 3: C

LEARANCES

TO

C

OMBUSTIBLES

7

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.

2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.

FIGURE 6: 45

°

TILT REFLECTOR

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

TF-120

8

8

60

54

21

21

153

138

TF-160

8

8

66

60

21

21

168

153

TF-200

10

8

74

64

26

21

188

163

TF-250

10

8

78

69

26

21

199

176

TF-300

12

8

84

74

31

21

214

188

TF-350

12

8

85

79

31

21

216

201

TF-380

12

8

85

79

31

21

216

201

FIGURE 7: U-TUBE, STANDARD REFLECTOR

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

TF-120

6

35

63

30

16

89

161

77

TF-160

6

38

69

37

16

97

176

94

TF-200

6

40

76

39

16

102

194

100

TF-250

6

46

79

43

16

117

201

110

TF-300

6

50

84

47

16

127

214

120

TF-350

8

54

87

51

21

138

221

130

TF-380

8

54

87

51

21

138

221

130

A

C

D

B

FIGURE 8: U-TUBE, 45

°

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

TF-120

8

8

60

42

21

21

153

107

TF-160

8

8

66

46

21

21

168

117

TF-200

8

8

74

52

21

21

188

133

TF-250

8

8

78

61

21

21

199

155

TF-300

8

8

84

66

21

21

214

168

TF-350

8

8

85

70

21

21

216

178

TF-380

8

8

85

70

21

21

216

178

B

C

D

A

Advertising