Roberts Gorden Vantage twin Fire Unitary Infrared Heater TF-250 User Manual

Page 14

Advertising
background image

TF-S

ERIES

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

8

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings and elbows.

2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.

*When installed in the first 10’ (3 m) on each side of the burner.
**Roberts-Gordon prohibits the installation of this heater for all unapproved applications.

FIGURE 9: U-TUBE, OPPOSITE 45

°

REFLECTOR

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

TF-120

8

54

60

22

21

138

153

56

TF-160

8

60

66

22

21

153

168

56

TF-200

10

64

74

22

26

163

188

56

TF-250

10

70

78

22

26

178

199

56

TF-300

12

74

84

22

31

188

214

56

TF-350

12

76

85

22

31

194

216

56

TF-380

12

76

85

22

31

194

216

56

A

C

D

B

FIGURE 10: 2-FOOT DECO GRILLE AND PROTECTIVE GRILLE

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

TF-120

6

35

63

35

16

89

161

89

TF-160

6

38

66

38

16

97

168

97

TF-200

6

40

71

40

16

102

181

102

TF-250

6

46

77

46

16

117

196

117

TF-300

6

50

80

50

16

127

204

127

TF-350

8

52

82

52

21

133

209

133

TF-380

8

52

82

52

21

133

209

133

A

C

D

B

FIGURE 11: LOWER CLEARANCE SHIELD*

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

TF-120

6

39

33

39

16

100

84

100

TF-160

6

40

38

40

16

102

97

102

TF-200

6

50

44

50

16

127

112

127

TF-250

6

54

48

54

16

138

122

138

TF-300

6

55

50

55

16

140

127

140

TF-350**

Unapproved

Unapproved

TF-380**

Unapproved

Unapproved

A

C

D

B

Advertising