Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace

10

EXTERIOR VENT TERMINATION LOCATIONS

INSTALLATION

.

B

B

B

B

A

C

V

V

V

V

V

V

V

A

A

V

Fixed

Fixed

Openable

Closed

Closed

Openable

N

L

B

E

B

M

D

F

K

H

j

V

ertical

Termination

V

V

ent

terminal

Area

where

terminal

is

not

permited

A

Air

supply

outlet

24"

V

A

G

Inside

corner

det

ail

V

24"

18"

V

ertical

Termination

A

=

Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm)

B

=

Clearance to window or door that may be opened *(12"/30cm)

C

=

Clearance to permanently closed window *(min. 12"/30cm)

D

=

Vertical clearance to ventilated soffit located above the terminal within a horizontal

distance of (24"/60cm) from the centerline of the terminal (min. 18"/46cm) check with

local code.

E

=

Clearance to unventilated soffit (min. 15"/38cm)

F

=

Clearance to outside corner: with

AstroCap

Termination Cap (min. 6"/15cm), with

Dura-Vent Termination Cap (12"/30cm)

G

=

Clearance to inside corner: with

AstroCap

Termination Cap (min. 6"/15cm), with Dura-

Vent Termination Cap (12"/30cm)

H

=

Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally from

the centerline of the regulator.

J=

Clearance to service regulator vent outlet *(min. 36"/90cm)

K

=

Clearance to non-mechanical air supply inlet to building or the combustion air inlet to

any other appliance *(12"/30cm)

L

=

Clearance to a mechanical air supply inlet *(min. 72"/1.8m)

M

=

Clearance above paved sidewalk or a paved driveway located on public property

*(min. 84"/2.1m)

N

=

Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)

Note:

- A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings a

nd serves both dwellings.

- Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

- If the vent termination is accessible, a certified guard shall be installed.

* As specified in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.