Installation, Vertical termination with co-linear flex system – Regency P33R-LP2 User Manual

Page 16

Advertising
background image

Regency P33R-2 Zero Clearance Rear Vent Direct Vent Gas Fireplace

16

VERTICAL TERMINATION

WITH CO-LINEAR FLEX SYSTEM

THE APPLIANCE MUST NOT BE

CONNECTED TO A CHIMNEY FLUE

SERVING A SEPARATE SOLID FUEL

BURNING APPLIANCE.

This appliance is designed to be attached to two
3" (76mm) co-linear aluminium flex running the
full length of the chimney. See the Venting
Arrangements on next page for minimum and
maximum heights.

Masonry chimneys may take various contours which the flexible liner will accommodate.
However, keep the flexible liner as straight as possible, avoid unnecessary bending.

The Air Intake pipe must be attached to the inlet air collar of the termination cap.

Required Parts:

Part #

Description

946-529

Co-linear DV Vertical
Termination Cap

948-305

3" Flex - 35 ft.

946-563

Co-Axial to Co-Linear Adapter Kit
which contains the following:
Co-linear Flex Adapter
Outer Pipe
Inner Pipe Adapter

510-994

Flue Adaptor

Alternate Approved Caps
980

Vertical Termination Cap

991

High Wind Cap

923GK 3" Co-linear Adapter with flashing

INSTALLATION

FPI Cabinet and/or Flat Wall Mantles
may be used in these applications
ensuring that clearances to com-
bustibles are maintained.