DATA4

'X' (ASCII CODE)

$0C - Last 4 chars tag description -------------------------------------------------- RX

DATA1

'X' (ASCII CODE)

DATA2

'X' (ASCII CODE)

DATA3

'X' (ASCII CODE)

DATA4

-

$0D - Alarm status ------------------------------------------------------------------------ RX

DATA1

LAL Status (0=No alarm - 1=Alarm active)

DATA1

HAL Status (0=No alarm - 1=Alarm active)

DATA1

-

DATA1

-

$1C - Firmware version ----------------------------------------------------------------- RX

DATA1

'X' (ASCII CODE)

DATA2

'X' (ASCII CODE)

DATA3

'X' (ASCII CODE)

DATA4

'X' (ASCII CODE)

15.3.2

Computer data setting from PC to OSP

Computer

OSP

Tx IDNAME

Rx IDNAME

Proceed if the name is acknowledged

Rx IDNAME

Tx IDNAME

If not, do not answer

Tx Instruction

Rx Instruction

Rx Instruction

Tx Instruction

Tx DATA 1

Rx DATA 1

Rx char

Tx char

Tx DATA 2

Rx DATA 2

Rx char

Tx char

Tx DATA 3

Rx DATA 3

Rx char

Tx char

Tx DATA 4

Rx DATA 4

Rx char

Tx char

Tx CHKSUM

Rx char

Rx char

Tx char

IDNAME, Instruction, DATA 1, DATA 2, DATA 3, DATA 4 and CHKSUM are 8-bit values (1 byte).
CHKSUM = DATA 1+DATA 2+DATA 3+DATA 4 .AND. FF

The above is useful to verify correct received data.
The minimum time-out of OSP is 3 seconds.
IDNAME is set to 1.

Writing values

$80 - Emissivity ---------------------------------------------------------------------------- TX

DATA1

0

DATA2

0

DATA3

0

DATA4

VALUE

VALUE = EMISSIVITY X 100

$82 - Tc type -------------------------------------------------------------------------------- TX

DATA1

0

DATA2

Tc type (0=Tc K - 1=Tc S)

DATA3

0

DATA4

0

$84 - HAL Setpoint------------------------------------------------------------------------ TX

DATA1

VALUE (HH)

DATA2

VALUE (H)

DATA3

VALUE (L)

Advertising