Setting i/o assignments, Switching banks by external signal input – Omron ZS-MDC User Manual

Page 54

Advertising
background image

3-16

Section 3

SETUP

ZS-MDC

User’s Manual

Section 3
Setting I/O Assignments

Setting I/O Assignments

Switching banks by external signal input

Set the task or function to the external input.

If you use SmartMonitor Zero, you can change the function assignments of IN2 and IN3 if [BANK] is
selected. For details, refer to the Help for SmartMonitor Zero.

FUN mode-[I/O SET]-[I/O SET]-[IN]

For bank inputs A and B, the bank can be selected in the following combinations.

• Bank switching is begun 0.5 seconds after the input state changes.
• At most it takes about 10 seconds to switch banks.
• During bank switching the BUSY output becomes ON.

Setting

Description

TASK

Select to task for enabling the external signal lead. Note, however, that reset input
and bank inputs affects tasks at all times.

Range: TASK1 to TASK4, TASK-ALL

FUNC

NORMAL

Select this to use external input function as in standard applications so far (default
value).

IN0

IN1

IN2

IN3

External trigger
(timing) input

Reset input

Unused

Zero reset input

BANK

Select this to switch banks using external inputs.

IN0

IN1

IN2

IN3

Bank input A

Bank input B

Unused

Zero reset input

Bank to be Selected

Bank input A

Bank input B

BANK1

OFF

OFF

BANK2

OFF

ON

BANK3

ON

OFF

BANK4

ON

ON