Cb 1200 pellet stove, E. vertical - internal - typical installation – Quadra-Fire CB1200M-MBK User Manual

Page 15

Advertising
background image

R

December 16, 2011

7014-179D

Page 15

CB 1200 Pellet Stove

We recommend a minimum of 60 in. (1.5m) vertical,

however above the eave is preferred.

Both installations are approved for mobile home instal-

lations. Must use 3 or 4 inch (76 to 102mm) “L” or

“PL” Listed pellet venting or listed double wall pipe and

Quadra-Fire outside air kit in mobile homes. Single

wall pipe is approved for residential installations only.

C. Vertical into Existing Class A Chimney

D. Through The Wall & Vertical - External

Firestop

Flashing

Rain Cap

6 in.

(152mm)

Min.

Non-combustible Hearth Pad

3 in. (76mm)

Min.

Clean-out

Cover

24 in. (610mm)

minimum

Ceiling Support

Class A Chimney

Connector Adapter

Top Vent Kit

Non-combustible Hearth Pad

Clean-out Cover

Tee

Wall Thimble

Support Bracket

every 60 in. (1524mm)

24 in. (610mm)

Minimum

Rain Cap

Flashing

2 in. (51mm) Minimum

6 in. (152mm)

Minimum

Figure 15.1

Figure 15.2

E. Vertical - Internal - Typical Installation

Firestop

Flashing

Rain Cap

6 in.

(152mm)

Min.

Non-combustible Hearth Pad

3 in. (76mm)

Min.

24 in.

(610mm)

Minimum

3 in. to 3 in.

(76-76mm)

Top Vent Kit

Clean-out Cover

Figure 15.3