Quadra-Fire QV-PIER User Manual

Page 25

Advertising
background image

25

Quadra-Fire • QV-PIER, QV-ST Series: HV-IPI • 2005-901 Rev. G • 2/06

4. Install Firestops

For Horizontal Runs - Firestops are REQUIRED on both
sides of a combustible wall through which the vent passes.

NOTE: Model DVP-TRAP does not need an exterior
firestop on an exterior combustible wall. The firestop is
built into the cap.

To install firestops for horizontal runs that pass through either
interior or exterior walls:

• Cut a 10” x 12” (254mm X 305mm) hole through the wall.

NOTE: The center of the hole is one (1) inch (25.4mm)
above the center of the horizontal vent pipe.

• Position the firestops on both sides of the hole previ-

ously cut and secure the firestops with nails or screws.

• The heat shields of the firestops MUST BE placed to-

wards the top of the hole.

• Continue the vent run through the firestops.

Figure 23. 10" x 12" Hole and Vent Pipe

Figure 24 Heat Shield, Interior & Exterior Firestops

TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT

EXTERIOR
FIRESTOP

INTERIOR

FIRESTOP

HEAT SHIELD

3. Install Support Brackets

Refer to Cinch Pipe and Termination Cap installation
instructions.

2. Continue Adding Vent Components

Refer to Cinch Pipe and Termination Cap installation in-
structions.

• Continue adding vent components, locking each succeed-

ing component into place.

• Ensure that each succeeding vent component is secure-

ly fitted and locked into the preceding component in the
vent system. Securing pipe sections with a maximum of
two screws is recommended.

• 90° elbows may be installed and rotated to any point

around the preceding component’s vertical axis. If an el-
bow does not end up in a locked position with the pre-
ceding component, attach with a minimum of two (2)
sheet metal screws.

NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.

10"

12"

INTERIOR

WALL SHIELD

For Vertical Runs - One ceiling firestop is REQUIRED at
the hole in each ceiling through which the vent passes.

To install firestops for vertical runs that pass through ceilings:

• Position a plumb bob directly over the center of the verti-

cal vent component.

• Mark the ceiling to establish the centerpoint of the vent.

• Drill a hole or drive a nail through this centerpoint.

• Check the floor above for any obstructions, such as wir-

ing or plumbing runs.

• Reposition the fireplace and vent system, if necessary,

to accommodate the ceiling joists and/or obstructions.

• Cut an 10-inch X 10-inch (254mm x 254mm) hole through

the ceiling, using the centerpoint previously marked.

• Frame the hole with framing lumber the same size as the

ceiling joists.

Advertising
This manual is related to the following products: