GAS

-

FIRED

WATER

BOILER

SERIES

1 & 2

— Control supplement & Service guide

Operating information

(continued)

Instructions in this supplement are based

on factory default parameter settings.

Parameter

Name

Range

Boiler display

Description

Details

Boiler

display

Display position

1st

2nd

3rd

4th

1

T3-Set

Storage DHW:

68 to 142°F

68 to 142

1

SETTING

Boiler outlet water temperature setpoint in DHW

s

mode is determined by adding parameter 1 to
parameter 33 (parameter 33 = 50°).

DO NOT set higher than 140°F. A

higher temperature setting could
cause a hazardous condition due to
excessive DHW temperature.

2

DHW System

DHW OFF

0

2

— BLANK —

— BLANK —

V

ALUE

Parameter 2 determines whether DHW heating

s

is activated.

4HE

PARAMETER

Weil-McLain does not recommend

setting this parameter

6!,5%

to

either “2” or “3” (continuous DHW
pump). This could result in a hazard-
ous condition — it would cause con-
stant circulation between the boiler
and the DHW heater.

DHW ON

1

DHW OFF

+ pump constant

2

DHW ON

+ pump constant

3

3

CH

System

CH OFF

0

3

— BLANK —

— BLANK —

V

ALUE

Parameter 3 determines whether central heating

s

is activated.

4HE

RAMETER

Select “1” to cycle the boiler circulator on central

s

heating calls for heat.

Weil-McLain does not recommend

setting this parameter

6!,5%

to

either “2” or “3” (continuous pump).
This could result in a hazardous
condition — it could supply water
to other zones when heat demand is
from a DHW tank.

CH ON

1

CH OFF

+ boiler pump

constant

2

CH ON

+ boiler pump

constant

3

4

T1

top

(Target

temperature)

70 to 192°F

70 to 192

4

SETTING

Constant boiler temperature operation (outside

s

sensor not connected) — T1top is the target
outlet water temperature at all times.

Outdoor reset operation (outdoor sensor con-

s

nected) — T1top is the maximum target tem-
perature for all outside temperatures.

Parameter reference table (also see

&IGURE

Figure 12, page 18)

2

— B

L

BL

VA