Troubleshooting, Control supplement & service guide – Weil-McLain ULTRA 230 User Manual
Page 28

28
Part number 550-100-029/0810
GAS
-
FIRED
WATER
BOILER
SERIES
1 & 2
— Control supplement & Service guide
Troubleshooting
(continued)
Instructions in this supplement are based
on factory default parameter settings.
HARD LOCKOUT condition
[Display flashes first digit, “E” and last two digits (code)]
Code
Reason for soft lockout
Corrective actions
(pressing RESET should restart boiler immediately)
Electrical shock hazard. Turn off power to boiler when working with
wiring or replacing any boiler component.
00
Flame detected on startup
1
Igniter may be cracked. Moisture gets in crack and may cause E-00.
2
Burner may be operating too hot due to incorrect combustion. Inspect flame during
operation following the procedure in Ultra Boiler Manual.
If flame is acceptable at both high and low fire, go to step 3, below.
If flame is not acceptable:
For propane boilers, verify propane orifice is correct and properly installed. See Ultra
s
Boiler Manual for procedure. Obtain and install propane orifice if necessary.
For correctly-orificed propane boiler or natural gas boiler, replace gas valve if burner
s
glows excessively.
3
Look into the burner inspection window after the boiler shuts down. If flame is still
present, gas valve may be leaking. Replace gas valve. BEFORE replacing valve check gas
line pressure coming to boiler. Pressure must not exceed 13 inches w.c. or valve damage
could occur.
02
Ignition failed through 5 attempts:
./
1
Check ignition electrode cable, electrode connector, spade connection at MCBA and
other connections.
Inspect ignition electrode cable and electrode for insulation damage.
s
Resistance of igniter wire should be 1000 ohms +/- 50 ohms. If resistance is more or
s
less, replace igniter wire.
Check ground lead from ground terminal strip to heat exchanger access cover.
s
02
Ignition failed through 5 attempts:
3PARK
1
Verify manual gas valve in boiler is open.
2
[Models 80 or 105 only] — Verify plastic line from gas valve to air inlet elbow is con-
nected to gas valve and elbow, and line is unobstructed, with no kinks
3
Check incoming gas pressure per Ultra Boiler Manual. If gas pressure is too high, the
gas valve regulator will lock up.
4
Verify gas lines are free of obstruction.
5
Purge gas lines of air if necessary.
6
Verify flue gas vent and air supply piping are correctly installed, in good condition and
there are no obstructions.
7
Check voltage to gas valve. It should be approximately 19 to 21 vdc during ignition
attempt.
8
Check gas meter to verify gas flows when gas valve is activated.
9
Remove and inspect/clean ignition electrode per Ultra Boiler Manual. Clean white oxides
if necessary. Replace ignition electrode if in poor condition or cannot be cleaned.
10
Ensure vent is clear. Restricted vent will not allow boiler to light.
Troubleshooting procedures — when display shows hard lockout code
&IGURE