Troubleshooting, Control supplement & service guide, Checking temperature sensors – Weil-McLain ULTRA 230 User Manual

Page 23

Advertising
background image

23

Part number 550-100-029/0810

GAS

-

FIRED

WATER

BOILER

SERIES

1 & 2

— Control supplement & Service guide

REVIEW OF LAST LOCKOUT CODE MESSAGE

To access parameters, view RPM speed and the last Error Code:

The boiler must be in “STBY” mode.

1.

Press and hold the STEP button.

2.

While holding STEP, press and hold the MODE button.

3.

Hold both buttons until CODE appears on the display. Release both buttons.

4.

Press the STEP button and a number will appear as C-**.

5.

Press the “+” or “–” buttons until the number changes to C-05.

6.

Press STORE. The display should blink one time.

7.

The control is now unlocked, ready to make parameter changes, view RPM speed and view the last error code.

8.

To view the last lockout code:

Press MODE until ERROR appears on the display, with the following information:

4HE

1.

The sequence when lockout occurred (example: 03 call for heat)

2.



3.

The return temperature at the time of lockout.

4.

4YPE

5.

Outdoor sensor status temperature if connected, –22 if not.

6.

Troubleshooting

(continued)

Checking temperature sensors

The boiler temperature sensors (flue, outdoor, return water and supply

1.

water) are all resistance-type devices.

The table at right shows the correct value for the sensor at various

2.

temperatures.

Use the resistance values at 32°F, 60°F, 70°F and 212°F to measure the

3.

sensor resistance at known temperatures (ice point, room temperature
and sea level boiling point). For ice point and boiling point, insert the
sensor in water at that temperature. Use an ohmmeter to read resistance
value.

To check whether the control module is correctly sensing temperature,

4.

you can use a resistance decade box. Connect the decade box temporarily
in place of a sensor and use the control module Information mode (see
page 19 for details) to read the temperature. The temperature should
be close to the value corresponding to the input resistance.

Sensor resistance values

Temp
(°F)

Sensor ohms

Temp
(°F)

Sensor ohms

Min

Max

Min

Max

32

34265

37871

130

3698

4088

40

27834

30764

140

3043

3364

50

21630

23907

150

2517

2782

60

16944

18727

160

2091

2311



13372

14780



1744

1928

80

10629

11747

180

1461

1615

90

8504

9399

190

1229

1359

100

6847

7568

200

1038

1147

110

5545

6129

210

880

972

120

4517

4992

212

851

941

Instructions in this supplement are based

on factory default parameter settings.