Control supplement & service guide – Weil-McLain ULTRA 230 User Manual

Page 43

Advertising
background image

43

Part number 550-100-029/0810

GAS

-

FIRED

WATER

BOILER

SERIES

1 & 2

— Control supplement & Service guide

Default parameter settings —

&IGURE

$/

Par.

No.

Parameter description

Ultra-80 thru -230

Ultra-310 ONLY

Standard (to 5500 feet)

High altitude

Standard (to 5500 feet)

High altitude

1

T3set DHW

140

140

140

140

2

DHW System

1

1

1

1

3

CH System

1

1

1

1

4

T1 Top CH-mode

190

190

190

190

5

T1 Foot CH-mode

70

70

70

70

6

T4 minimum

32

32

32

32

7

T4 maximum

70

70

70

70

8

T4 frost protection

-22

-22

-22

-22

9

T4 correction

0

0

0

0

10

T blocking

70

70

70

70

11

Booster time

10

10

10

10

12

T parallel shift

0

0

0

0

13

Maximum fanspeed CH

Display shows

value in 100’s

Example:

52 = 5200 rpm

52(00)

52(00)

58(00)

58(00)

15

Maximum fanspeed DHW

52(00)

52(00)

58(00)

58(00)

17

Minimum fanspeed

13(00)

20(00)

14(00)

20(00)

19

Ignition fanspeed

27(00)

35(00)

23(00)

32(00)

20

CH postpump time

0

0

0

0

21

DHW postpump time

03

03

03

03

22

CH modulation hysteresis on

8

8

8

8

23

CH modulation hysteresis off

4

4

4

4

24

DHW modulation hysteresis on

8

8

8

8

25

DHW modulation hysteresis off

4

4

4

4

26

DHW detection hysteresis on

8

8

8

8

27

DHW detection hysteresis off

8

8

8

8

28

CH blocking time

06

06

06

06

29

DHW blocking time

0

0

0

0

30

DHW -> CH blocking time

0

0

0

0

31

Modulate back difference T1 - T2

44

44

44

44

32

RMCI Address

0

0

0

0

33

Tplus: Setvalue additional for DHW

50

50

50

50

34

2nd CH-circuit (1st digit)

00

00

00

00

34

CH type (2nd digit)

35

DHW 3wayvalve or pump (1st digit)

13

13

13

13

35

DHW-type (2nd digit)

36

Manual fanspeed

-1

-1

-1

-1

37

PWM-pump level (1st digit)

41

41

41

41

37

PWM-pump level (2nd digit)

38

Tset hold boiler warm

32

32

32

32

39

Ttop for 2nd CH circuit

94

94

94

94

40

Tfoot for 2nd CH circuit

50

50

50

50

41

Thysterese for 2nd CH circuit

36

36

36

36

42

Pump settings for CH and DHW

21

21

21

21

42

Minimum Off Cycle

See Figure 25, page 42 for procedure to access Parameter settings.