Troubleshooting

(continued)

Instructions in this supplement are based

on factory default parameter settings.

HARD LOCKOUT condition

[Display flashes first digit, “E” and last two digits (code)]

04

Voltage lost after lockout occurred
or AC voltage fluctuations on
incoming power

1

Control module will only restart with manual reset, even after power loss.

Code 04 occurs if power is interrupted while another error is present or due to power

s

input fluctuations.

2

Incoming power fluctuations may cause MCBA module to go into E-04 hard error
code.

This can occur due to power failure, brown-out or poor electrical input from a back-

s

up generator.
To reduce shutdowns due to poor power conditions, install Weil-McLain part number

s

383-500-021, Time Delay Relay (3 minute incoming power time delay) to give incom-
ing power time to stabilize before powering boiler.

3

In severe cases of power fluctuations, Time Delay Relay may not solve E-04.

If so, very good incoming power line filter or Uninterruptible Power Source (UPS)

s

may correct.

05

Internal Control or Display error

1

Replace display and display ribbon cable.

2

Replace control module.

06

Internal Control Failure

1

Reset control and retry. If problem persists, replace control module.

07

Gas valve relay error

1

Gas valve wiring may be shorted to ground. Check continuity to ground

2

Defective gas valve. Measure resistance between outer two pins on gas valve — should
be approximately 50 ohms. Resistance from each pin to ground must be infinity.

08

Internal Control Failure

1

Reset control and retry. If problem persists, replace control module.

09

Internal Control Failure

1

Reset control and retry. If problem persists, replace control module.

11

EEPROM Error

1

Ignition interference.

2

Replace control module.

12

External limit open (between
terminal 6 and 8)

1

Check low water cut-off, limit controls, etc. wired between terminals 6 and 8.

13

Usually indicates a sensor problem

1

Measure the resistance of each of the sensors — return, supply and flue. See page 23 for
sensor resistance values. Replace sensor(s) if necessary.

14

Supply water sensor problem

1

Measure the resistance of each of the supply sensor. See page 23 for sensor resistance
values. Replace sensor if necessary.

15

Internal control failure

1

Reset control and retry. If problem persists, replace control module.

16

17

&IGURE

Troubleshooting procedures — when display shows hard lockout code (continued)