Troubleshooting, Control supplement & service guide – Weil-McLain ULTRA 230 User Manual
Page 30

30
Part number 550-100-029/0810
GAS
-
FIRED
WATER
BOILER
SERIES
1 & 2
— Control supplement & Service guide
Troubleshooting
(continued)
Instructions in this supplement are based
on factory default parameter settings.
HARD LOCKOUT condition
[Display flashes first digit, “E” and last two digits (code)]
04
Voltage lost after lockout occurred
or AC voltage fluctuations on
incoming power
1
Control module will only restart with manual reset, even after power loss.
Code 04 occurs if power is interrupted while another error is present or due to power
s
input fluctuations.
2
Incoming power fluctuations may cause MCBA module to go into E-04 hard error
code.
This can occur due to power failure, brown-out or poor electrical input from a back-
s
up generator.
To reduce shutdowns due to poor power conditions, install Weil-McLain part number
s
383-500-021, Time Delay Relay (3 minute incoming power time delay) to give incom-
ing power time to stabilize before powering boiler.
3
In severe cases of power fluctuations, Time Delay Relay may not solve E-04.
If so, very good incoming power line filter or Uninterruptible Power Source (UPS)
s
may correct.
05
Internal Control or Display error
1
Replace display and display ribbon cable.
2
Replace control module.
06
Internal Control Failure
1
Reset control and retry. If problem persists, replace control module.
07
Gas valve relay error
1
Gas valve wiring may be shorted to ground. Check continuity to ground
2
Defective gas valve. Measure resistance between outer two pins on gas valve — should
be approximately 50 ohms. Resistance from each pin to ground must be infinity.
08
Internal Control Failure
1
Reset control and retry. If problem persists, replace control module.
09
Internal Control Failure
1
Reset control and retry. If problem persists, replace control module.
11
EEPROM Error
1
Ignition interference.
2
Replace control module.
12
External limit open (between
terminal 6 and 8)
1
Check low water cut-off, limit controls, etc. wired between terminals 6 and 8.
13
Usually indicates a sensor problem
1
Measure the resistance of each of the sensors — return, supply and flue. See page 23 for
sensor resistance values. Replace sensor(s) if necessary.
14
Supply water sensor problem
1
Measure the resistance of each of the supply sensor. See page 23 for sensor resistance
values. Replace sensor if necessary.
15
Internal control failure
1
Reset control and retry. If problem persists, replace control module.
16
17
&IGURE
Troubleshooting procedures — when display shows hard lockout code (continued)