2.0 SPECIFICATIONS

2.1 ANALOG INPUTS
Number of channels:

32 for PID control, 48 total with reed multiplexer,
96 total with solid state.

Multiplexing:

three wire reed relay, guarded inputs. two wire solid
state.

A/D converter:

integrating voltage to frequency.

Loop update:

each loop 2 times per second, reed modules; 1 time
per second solid state.

Input isolation:

optical coupling.

Input resolution:

0.02% full scale [Approximately 12.7uv].

Temp. coefficient:

.005% per degree.

Measurement accuracy:

+0.1% full scale.

Thermocouple break:

up scale standard.

Standard input types:

All are present in every system: select by command
from host, any order, any mix:

Thermocouple ranges:

J: -350 to 1400 F K: -450 to 2500 F

[200 ohms max.]

T: -450 to 750 F E: -450 to 1450 F

R: 0 to 3200 F S: 0 to 3200 F

SYSTEM 32 must be operating between 0 and 50

degrees C for full T/C ranges.

Thermocouple scaling:

Degrees F [convert to degrees C in computer].

Other Inputs:

-10mv to 60mv input range with provision for
scaling resistors and bridges for Voltage/Current
andRTD inputs.

Linear Scaling:

-16.7% to 100% for -10 to 60 mv

Voltage Ranges:100v max:

Select resistors for 0 to 10v, 0 to 5v, 2 to 10v, etc.
as required.

Current Ranges:

Select resistors for 0 to 10ma, 4 to 20ma, 10 to
50ma, etc. as required.

Bridge Excitation:

10v+.13%, at 50ma max [temperature coefficient
15ppm/degree C max].

Optional input types:

Other T/C types, Non-contact infrared, 2, 3, or 4-
wire RTD, Carbon Potential.

Advertising