2.2 OPERATING PARAMETERS
Independently set for each loop through serial interface.

Input type:

any standard type (see above), any mix.

Gain:

0 to 255 proportional; 0 to 510 on/off. Proportional
Band: Direct reading in engineering units of the
loop range.

Integral:

0 to 1020 seconds. Reset: .05 to 60 Repeats/Min. [4
sec. resolution].

Derivative:

0 to 255 sec. Rate: .01 to 4.25 Min.

Digital Filter:

Averages last 0 to 255 outputs. [0- 127.5 sec. time
constant].

Setpoint:

+span. Resolution: 0.01%; 0.1o for T/C.
ANASOFT resolution: 0.1%; 1o for T/C.

Deviation band alarm:

0 to +25% Full Scale; 0 to +250o T/C.

Control output level:

Direct or reverse acting, 0-100%.

Manual output:

0 to 100% (0.4% resolution).

2.3 REPORTING PARAMETERS
The computer can request any of the following for any loop:

Operating parameters:

all of the above

Analog inputs:

measured values

Digital I/O:

status

2.4 COMMUNICATIONS
Types:

RS-232 or 20ma current loop, factory set; optional
RS422 or RS485

Baud rate:

2400 or 9600, switch selectable

Protocol:

Form of ANSI X3.28-1976 [Allen Bradley
compatible]

Character set:

ANSI X3.4

Error check:

CRC or BCC, switch selectable.

Isolation:

optical for all types including RS-232.

Display:

LED indicates communication active.