10.4.1 Processor Reset
This Error Code is returned after :
ƒ

Power-up reset

ƒ

The watchdog timer resets the Master processor

ƒ

The Master processor resets the Slave processor

10.4.2 Command Error
This Error Code is returned when the A32PID receives a command that is
not a Block Read or a Block Write.

10.4.3 Data Boundary Error
This Error Code is returned when:
ƒ

A Read command attempts to read beyond the 32 byte boundary of

byte-size variables

ƒ

A Read command attempts to read beyond the 64 byte boundary of

word-size variables

ƒ

A Read command is received that specifies the number of bytes to read

as 0

ƒ

AWritecommand attempts to write beyondthe32 byte boundary of

byte-size variables

ƒ

A Write command attempts to write beyond the 64 byte boundary of

word-size variables

10.5. Data Table Addresses

Addresses

Variable

Number Size

Hex Byte Range Octal Word Range

Prop. Gain

32

Byte

0100 - 011F

200 - 217

Rate

32

Byte

0120 - 013F

220 - 237

Reset

32

Byte

0140 - 015F

240 - 257

Input Type

32

Byte

0160 - 017F

260 - 277

Output Value

32

Byte

0180 - 019F

300 - 317

Output Type

32

Byte

01A0 - 01BF

320 - 337

Output Filter

32

Byte

01C0 - 01DF

340 - 357

Cycle Time

32

Byte

01E0 - 01FF

360 - 377

Alarm Deviation

32

Byte

0200 - 021F

400 - 417

Setpoint

32

Word

0220 - 025F

420 - 457

Measured Value

32

Word

0260 - 029F

460 - 517

Ambients

08

Byte

02A0 - 02A7

520 - 523

Digital I/O's

01

Byte

02A8

524

Alarm Status

08

Byte

02B0 - 02B7

530 - 533

Heater Check

33

Byte

02BC

536

EEROM Save

---

-----

02BE

537

DACQ Input Type

64 Byte

02C0 - 02FF

540 - 577

DACQ Meas. Val.

64 Word

0300 - 037F

600 - 677